Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NOAA SEAFOOD INSPECTION PROGRAM

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NOAA SEAFOOD INSPECTION PROGRAM in 7600 SAND POINT WAY NE, BUILDING 32, SEATTLE, WA 98115 (NAICS 541990). OSHA activity number 339599342.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Noaa Seafood Inspection Program — free Get an email when a new federal OSHA severe-injury report for Noaa Seafood Inspection Program is published. One employer, no account, unsubscribe in one click.
Site address
7600 SAND POINT WAY NE, BUILDING 32
City
SEATTLE
State
WA
ZIP
98115
Mailing
7600 SAND POINT WAY NE, SEATTLE, WA 98115
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541990
Employees
17
Ownership type
D

5 citations on file for this inspection.

1910.303 B02

Repeat Gravity 1 1 instance 1 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:   a) Second Floor Office, where two relocatable power taps were daisy chained and used to supply power to computer equipment.   The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 107939 citation no. 2, item no. 1, issued on November 15, 2011 with respect to a workplace at Mukilteo, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097335, citation no. 2, item no. 1, issued on April 28, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097343, citation no. 1, item no. 1, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no.309097319, citation no. 2, item no. 2, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097384, citation no. 1, item no. 1, issued on April 27, 2010 with respect to a workplace at Seattle, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096287, citation no. 2, item no. 1, issued on October 2, 2009 with respect to a workplace at Port Orchard, WA.
Recent events (1)
  • — Z (R) $0

1910.305 G01 IV A

Repeat Gravity 1 2 instances 17 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:   a)  Office suite, where flexible cords used as a substitute for fixed wiring included:   1. Administrative Office, where a gray extension cord was used to supply power to the Comfort Aire air conditioner.   2. Inspectors Office, where a black extension cord was used to supply power to the Sharp Business System Printer.   The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829.015 citation no. 2, item no. 4, issued on June 4, 2013 with respect to a workplace at Pasco, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 107939 citation no. 1, item no. 1, issued on November 15, 2011 with respect to a workplace at Mukilteo, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097285 citation no. 1, item no. 7, issued on April 27, 2010 with respect to a workplace at Seattle, WA.
Recent events (1)
  • — Z (R) $0

1910.303 G02 I D

Repeat Gravity 1 3 instances 17 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i)(D): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by  elevation of 2.44 m (8.0 ft) or more above the floor or other working surface:   a) Office Suite, where florescent light fixtures equipped with unguarded bulbs included:   1. Cage, florescent light fixtures located above the door measured 7 feet 8 inches above floor level.   2. Cage, where florescent light fixtures located above the file cabinets measured 7 feet 3 inches above floor level.   3. Cage, where boxes stored on top of the filing cabinets measured 8 inches below the florescent light fixtures.   The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829.015 citation no. 2, item no. 6, issued on June 4, 2013 with respect to a workplace at Pasco, WA.     The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309096287, citation no. 2, item no. 2, issued on October 2, 2009 with respect to a workplace at Port Orchard, WA.
Recent events (1)
  • — Z (R) $0

1910.36 G02

Other-than-serious 2 instances 17 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:   a) Office Suite, where exit accesses not maintained included:   1. First Floor Storage Room, where the placement of items including chairs, trash cans, and baskets reduced the aisleway width to 9-13 inches.   2. Second Floor Storage Room, where the placement of items including, boxes and stacks of paper reduced the aisleway width to 5-19 inches.
Recent events (1)
  • — Z (O) $0

1910.37 B05

Other-than-serious 2 instances 17 exposed
Issued
Apr 1, 2014
Abate by
May 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g., closet):   a) Office Suite, where the doors not equipped with signage included:   1. Administrative Office, blue door to the warehouse.   2. Inspectors Office, blue door to the warehouse.
Recent events (1)
  • — Z (O) $0

View Noaa Seafood Inspection Program's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339599342.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.