SEATTLE, WA —
OSHA Inspection: NOAA DIVING CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NOAA DIVING CENTER in 7600 SAND POINT WAY NE, SEATTLE, WA 98115 (NAICS 541990). OSHA activity number 339600785.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NOAA DIVING CENTER
- Site address
- 7600 SAND POINT WAY NE
- City
- SEATTLE
- State
- WA
- ZIP
- 98115
- Mailing
- 7600 SAND POINT WAY NE, SEATTLE, WA 98115
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541990
- Employees
- 13
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.147 C06 II
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection: a) The employer did not certify that the periodic lockout tagout inspection for the compressors had been performed by recording the name, date and type of equipment recertified.
Recent events (1)
- — Z (S) $0
1910.23 C01
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:Note: Toeboards are only required when persons can pass, there is moving equipment or there is equipment with which falling materials could create a hazard. a) Building 8, Diving Center; A guardrail system on the blue metal platform on the second floor was missing a midrail, exposing employees to potential fall hazards. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829 citation 2, item 1, issued on June 4, 2013 with respect to a workplace at Pasco, Washington . The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097400 citation 1, item 1, issued on April 27, 2010 with respect to a workplace at Seattle, Washington . The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097327 citation 1, item 2, issued on April 27, 2010 with respect to a workplace at Seattle, Washington.
Recent events (1)
- — Z (R) $0
1910.147 C06 I
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: a) The employer did not conduct an annual inspection of the lockout tagout program for the compressors. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829 citation 2, item 2B, issued on June 4, 2013 with respect to a workplace at Pasco, Washington. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097400 citation 1, item 3B, issued on April 27, 2014 with respect to a workplace at Seattle, Washington.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Building 8, Diving Break Room; Two white relocatable power taps were daisy chained and mounted in a cabinet, violating the UL listing and labeling. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. The UL listing also stated that relocatable power taps are not to be mounted. This exposes employees to possible electrical fire hazards. (b) Building 8, Diving Boat Bay; A Maytag washing machine was plugged into an extension cord. The UL listing states that extension cords are to be used on a temporary basis only. This exposed employees to possible electrical fire hazards.
Recent events (1)
- — Z (R) $0
1910.305 J01 I
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Rosettes and cleat-type lampholders and receptacles located less than 2.44 m (8 feet) above the floor had exposed terminals: a) Building 8, Diving Center, Exercise Room; A florescent light bulb was located 7 feet 2 inches from the floor and was not guarded. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 107939 citation 2, item 3, issued on November 15, 2011 with respect to a workplace at Mukilteo, Washington. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097285 citation 1, item 8, issued on April 27, 2010 with respect to a workplace at Seattle, Washington. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 309097319 citation 1, item 6, issued on April 27, 2010, with respect to a workplace at Seattle, Washington.
Recent events (1)
- — Z (R) $0
1910.22 D01
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate. a) Building 8, Diving Center Boat Bay; Tarps and piping was stored on top of a metal caged storage area, and the overhead load rating was not posted.
Recent events (1)
- — Z (O) $0
1910.37 B04
- Issued
- Apr 2, 2014
- Abate by
- May 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) Building 8, Diving Center Managers Office; There were two or more doors in the office suite, and the door which lead to the exit corridor was not marked with an exit sign. b) Building 8, Diving Center Exercise Room; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign. c) Building 8, Diving Center Managers Office adjacent to the Exercise Room; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign. d) Building 8, Diving Break Room; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign. e) Building 8, Diving Medical Officers Office; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign. f) Building 8, Chamber Room; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign. g) Building 8, Diving Equipment Room/ Office; There were two or more doors in the room, and the door which lead to the exit corridor was not marked with an exit sign.
Recent events (1)
- — Z (O) $0
More inspections at Noaa Diving Center
View Noaa Diving Center's full OSHA safety record →
More inspections in this industry (NAICS 541990)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339600785.