SEATTLE, WA ·
OSHA Inspection: NOAA OCEAN MEDIA CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NOAA OCEAN MEDIA CENTER in 7600 SAND POINT WAY NE BUILDING 3, SEATTLE, WA 98115 (NAICS 541710). OSHA activity number 339600850.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NOAA OCEAN MEDIA CENTER
- Site address
- 7600 SAND POINT WAY NE BUILDING 3
- City
- SEATTLE
- State
- WA
- ZIP
- 98115
- Mailing
- 7600 SAND POINT WAY NE, SEATTLE, WA 98115
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 541710
- Employees
- 2
- Ownership type
- Federal government (D)
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Apr 1, 2014
- Abate by
- May 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Building 3, Suite 1003-1003A; An APC Network AIR 100 air conditioner was plugged into a relocatable power tap, violating the power taps UL listing and labeling. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. (b) Building 3, Suite 1003-1003A; A Kenmore refrigerator was plugged into a relocatable power tap, violating the power taps UL listing and labeling. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 906829 citation 2, item 4, issued on June 4, 2013 with respect to a workplace at Pasco, Washington. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 915685 citation 1, item 1, issued on July 26, 2013 with respect to a workplace at Long Beach, California. The National Oceanic and Atmospheric Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 915443 citation 1, item 2, issued on August 9, 2013 with respect to a workplace at Long Beach, California.
Recent events (1)
- · Z (R) $0
1910.36 G02
- Issued
- Apr 1, 2014
- Abate by
- May 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a) Building 3, Vault Storage Area; The aisleway between metal shelving and stored items was 21 inches wide.
Recent events (1)
- · Z (O) $0
1910.37 B04
- Issued
- Apr 1, 2014
- Abate by
- May 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: a) Suite 1003A; An exit sign was not in the line of sight in the media workspace. b) Suite 1003: An exit sign was not over the door which lead to an exit corridor. There were multiple doors in the work space. c) Suite 1003; A directional sign was not on the east wall, directing employees and visitors to the nearest exit.
Recent events (1)
- · Z (O) $0
More inspections in this industry (NAICS 541710)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339600850.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.