HARRISON, OH ·
OSHA Inspection: NARDELLI ELECTRIC, INC.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of NARDELLI ELECTRIC, INC. in 10515 B HARRISON AVE, HARRISON, OH 45030 (NAICS 238210). OSHA activity number 339603482.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NARDELLI ELECTRIC, INC.
- Site address
- 10515 B HARRISON AVE
- City
- HARRISON
- State
- OH
- ZIP
- 45030
- Mailing
- 4240 PICTUREVIEW, CINCINNATI, OH 45247
What kind of inspection was it?
- Inspection type
- Programmed Related (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.403 I02 I
- Issued
- Mar 18, 2014
- Abate by
- Mar 24, 2014
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. Located along the rear interior area of the commercial structure adjacent to a stairway observed in use there is an energized Square D breaker panel board #NF442L6C without the dead front trim panel cover installed exposing live electrical parts therein operating at 110v or greater.
Recent events (2)
- · I (S) $1960
- · Z (S) $2800
1926.405 G02 IV
- Issued
- Mar 18, 2014
- Abate by
- Mar 24, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Strain relief. Flexible cords shall be connected to devices and fittings so that strain relief is provided which will prevent pull from being directly transmitted to joints or terminal screws. Located along the rear interior area of the commercial structure there is a 480v SAES #780 Pro Floor Grinder and GE transformer #918368872 observed in use energized powered connected to electrical service panel by black flex cord to a Square D panel board # NF442L6C with the dead front trim panel not in place and transformer conductors to energized panel device without a strain relief coupler/clamp on the flex cord to prevent direct transmission pull to conductor joints at the panel.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339603482.