Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WESTMORELAND ELECTRIC, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of WESTMORELAND ELECTRIC, INC. in 2831 WASHINGTON AVE., CLEARFIELD, PA 16830 (NAICS 238210). OSHA activity number 339624108.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Westmoreland Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Westmoreland Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2831 WASHINGTON AVE.
City
CLEARFIELD
State
PA
ZIP
16830
Mailing
193 CENTRAL ROAD, TARRS, PA 15688
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
A

2 citations on file for this inspection.

1926.405 A02 II B

Other-than-serious 1 instance 10 exposed
Issued
Aug 22, 2014
Abate by
Sep 18, 2014
Penalty
Initial $1,890 · Current $1,100 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors were located where the conductors would be subject to physical damage and the open conductors were not fastened at intervals not exceeding 10 feet (3.05 m):    a) construction area of locker room adjacent to the gymnasium at Clearfield Area High School, 2831 Washington Ave. in Clearfield, PA.  On or about March 6, 2012, the Type NM Cables, used as temporary wiring in the work area were not secured along the wall area. The conductors were secured/coiled at the ceiling but were not secured as they proceeded down and along the wall toward the floor. The conductors were subjected to damage from construction personnel/equipment moving through the area.
Recent events (2)
  • — I (O) $1100
  • — Z (S) $1890

1926.403 B02

Other-than-serious 1 instance 10 exposed
Issued
Aug 22, 2014
Abate by
Sep 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) construction area of locker room adjacent to the gymnasium at Clearfield Area High School, 2831 Washington Ave. in Clearfield, PA.  On or about March 6, 2012, the Type NM Cables, used as temporary wiring in the work area were not secured along the wall area. The conductors were secured/coiled at the ceiling but were not secured as they proceeded down and along the wall toward the floor. The conductors were subjected to damage from construction personnel/equipment moving through the area.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Westmoreland Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339624108.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.