Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: C AND C POWERLINE, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of C AND C POWERLINE, INC. in 16770 REBAR ROAD, BALDWIN, FL 32234 (NAICS 238210). OSHA activity number 339632895.

Watch C AND C Powerline, INC. — free Get an email when a new federal OSHA severe-injury report for C AND C Powerline, INC. is published. One employer, no account, unsubscribe in one click.
Site address
16770 REBAR ROAD
City
BALDWIN
State
FL
ZIP
32234
Mailing
12035 PALM LAKE DRIVE, JACKSONVILLE, FL 32218
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
76
Ownership type
A

2 citations on file for this inspection.

1910.269 A02 III

Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $4900.00 · Current $4200.00 Reduced
29 CFR 1910.269(a)(2)(iii): The employer did not determine through regular supervision and through inspections conducted on at least an annual basis, that each employee was complying with the safety related work practices required by this section:    a. On or about March 14, 2014, the employer did not determine through regular supervision and through inspections, conducted on at least an annual basis, that each employee was complying with the safety related work practices when three employees cut into an energized 23kV primary high voltage power line and resulted in an electrical arc flash that injured two employees.
Recent events (3)
  • — F (S) $4200
  • — C (S) $4900
  • — Z (S) $4900

1910.269 M03 V

Serious Gravity 10 1 instance 3 exposed
Issued
Penalty
Initial $4900.00 · Current $4200.00 Reduced
29 CFR 1910.269(m)(3)(v): After the applicable requirements in paragraphs (m)(3)(i) through (m)(3)(iv) of 29 CFR 1910.269(m)(3) have been followed and the employee in charge of the work has been given a clearance by the system operator, the lines and equipment to be worked were not tested to ensure that they are de-energized:      a. On or about March 14, 2014, the employee in charge did not test an exposed underground 23kV primary high voltage power line to ensure that it was de-energized prior to working on the line and resulted in an electrical arc flash that injured two employees.
Recent events (3)
  • — F (S) $4200
  • — C (S) $4900
  • — Z (S) $4900

View C AND C POWERLINE, INC.'s full OSHA safety record →