OSHA Inspection: XTO ENERGY INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of XTO ENERGY INC. in 245 PRIVATE ROAD 7651, HAWKINS, TX 75765 (NAICS 211112). OSHA activity number 339637431.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch XTO Energy INC. for free Get an email when a new federal OSHA severe-injury report for XTO Energy INC. is published. One employer, no account, unsubscribe in one click.
Establishment
XTO ENERGY INC.
Site address
245 PRIVATE ROAD 7651
City
HAWKINS
State
TX
ZIP
75765
Mailing
245 PRIVATE ROAD 7651, HAWKINS, TX 75765
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
211112
Employees
45
Ownership type
Private (A)

2 citations on file for this inspection.

1910.119 J04 I

Serious Gravity 10 1 instance 33 exposed
Issued
Sep 3, 2014
Abate by
Nov 1, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.119(j)(4)(i):  Inspections and tests were not performed on process equipment:       The employer did not ensure that all required inspections and tests were performed.      A.    The violation occurred in the Gas Processing/NRU Facility on or about March 18, 2014 and times prior thereto where the employer failed to ensure that all applicable inspections and tests were performed in accordance with the employer's mechanical integrity program.  Identified process equipment pressure vessels:        a.     HBG-230 (Heat Exchanger)  b.     Tank 38 (Butane)  c.     Tank 40 (Slop Oil)  d.     Tank 32 (Propane)  e.     MBF-114 (Interstage Suction Scrubber)
Recent events (2)
  • · I (S) $7000
  • · Z (S) $7000

1910.119 J04 III

Serious Gravity 10 2 instances 33 exposed
Issued
Sep 3, 2014
Abate by
Dec 1, 2014
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience.      The employer did not ensure the frequency of inspections and tests were followed.      A. The violation occurred in the Gas Processing/NRU Facility on or about March 18, 2014 and times prior thereto where the employer failed to ensure the frequency of testing and inspections safety instrumented systems were conducted in accordance with the safety integrity level analysis and the employer's mechanical integrity program:      a.     Interlock/SIS 326  b.     Interlock/SIS 329  c.     Interlock/SIS 100  d.     Interlock/SIS 111  e.     Interlock/SIS 120  f.      Interlock/SIS 180  g.     Interlock/SIS 190  h.     Interlock/SIS 193  i.      Interlock/SIS 268