HAWKINS, TX ·
OSHA Inspection: XTO ENERGY INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of XTO ENERGY INC. in 245 PRIVATE ROAD 7651, HAWKINS, TX 75765 (NAICS 211112). OSHA activity number 339637431.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- XTO ENERGY INC.
- Site address
- 245 PRIVATE ROAD 7651
- City
- HAWKINS
- State
- TX
- ZIP
- 75765
- Mailing
- 245 PRIVATE ROAD 7651, HAWKINS, TX 75765
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 211112
- Employees
- 45
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1910.119 J04 I
- Issued
- Sep 3, 2014
- Abate by
- Nov 1, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment: The employer did not ensure that all required inspections and tests were performed. A. The violation occurred in the Gas Processing/NRU Facility on or about March 18, 2014 and times prior thereto where the employer failed to ensure that all applicable inspections and tests were performed in accordance with the employer's mechanical integrity program. Identified process equipment pressure vessels: a. HBG-230 (Heat Exchanger) b. Tank 38 (Butane) c. Tank 40 (Slop Oil) d. Tank 32 (Propane) e. MBF-114 (Interstage Suction Scrubber)
Recent events (2)
- · I (S) $7000
- · Z (S) $7000
1910.119 J04 III
- Issued
- Sep 3, 2014
- Abate by
- Dec 1, 2014
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. The employer did not ensure the frequency of inspections and tests were followed. A. The violation occurred in the Gas Processing/NRU Facility on or about March 18, 2014 and times prior thereto where the employer failed to ensure the frequency of testing and inspections safety instrumented systems were conducted in accordance with the safety integrity level analysis and the employer's mechanical integrity program: a. Interlock/SIS 326 b. Interlock/SIS 329 c. Interlock/SIS 100 d. Interlock/SIS 111 e. Interlock/SIS 120 f. Interlock/SIS 180 g. Interlock/SIS 190 h. Interlock/SIS 193 i. Interlock/SIS 268
Recent events (2)
- · I (S) $7000
- · Z (S) $7000
More inspections at XTO Energy INC.
View XTO Energy INC.'s full OSHA safety record →
More inspections in this industry (NAICS 211112)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339637431.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.