2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: PARK ELECTRIC, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PARK ELECTRIC, INC. in 450 OAK TREE AVENUE, SOUTH PLAINFIELD, NJ 07080 (NAICS 238210). OSHA activity number 339639056.

Watch Park Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Park Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
PARK ELECTRIC, INC.
Site address
450 OAK TREE AVENUE
City
SOUTH PLAINFIELD
State
NJ
ZIP
07080
Mailing
1645 W. FRONT STREET, PLAINFIELD, NJ 07063
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

2 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.333(a)(1): The employer failed to deenergize live parts to which an employee may be exposed before the employee works on or near them:  Location: 450 Oak Tree Avenue, South Plainfield, NJ 07080. The employer did not ensure that electrical equipment was deenergized prior to employee(s) working on or in it. Thereby exposing employee(s) to shock, burns and electrocution while working with energized parts.     a)    Employee(s) were working on, and in, an energized 1200 Amp Main Distribution Panel, when arc flash occurred resulting in the employee receiving burns.   Incident occurred on or about 02/20/14.
Recent events (3)
  • — R (S) $2800
  • — C (S) $2800
  • — Z (S) $2800

1910.335 A01 I

Serious Gravity 10 1 instance 1 exposed
Issued
Penalty
Initial $2800.00 · Current $2800.00
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with, and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed:   Location:  450 Oak Tree Avenue, South Plainfield, NJ 07080 The employer did not ensure that proper electrical protective equipment, such as but not limited to rated electrical gloves and flame retardant clothing,  was used or provided to employee(s) working on an energized electrical equipment. Thereby exposing employees to shock, burns and electrocution hazards.    a) Employee(s) working on an energized 1200 Amp Main Distribution Panel, when arc flash occurred resulting in the employee receiving  burns while working with energized parts  Incident occurred on or about 02/20/14
Recent events (3)
  • — R (S) $2800
  • — C (S) $2800
  • — Z (S) $2800