EASTPORT, ME —
OSHA Inspection: BORDER ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of BORDER ELECTRIC, INC. in ROUTE 190, EASTPORT, ME 04631 (NAICS 238210). OSHA activity number 339645194.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BORDER ELECTRIC, INC.
- Site address
- ROUTE 190
- City
- EASTPORT
- State
- ME
- ZIP
- 04631
- Mailing
- 337 NORTH STREET, CALAIS, ME 04619
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.403 D01
- Issued
- Mar 26, 2014
- Abate by
- Apr 3, 2014
- Penalty
- Initial $2,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.403(d)(1): Electric equipment was not firmly secured to the surface on which it was mounted: Guilford Mill Building, Panel T4 - The two receptacle outlet boxes and cable were not firmly secured.
Recent events (2)
- — I (S) $1500
- — Z (S) $2000
1926.404 E01 I
- Issued
- Mar 26, 2014
- Abate by
- Apr 3, 2014
- Penalty
- Initial $2,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.404(e)(1)(i): Conductors and equipment rated 600 volts, nominal, or less were not protected from overcurrent in accordance with their ability to safely conduct current: Guilford Mill Building, Panel T4 - The 12 gauge conductors and receptacle outlets, rated for 20 amps, were connected to 50 amp breakers.
Recent events (2)
- — I (S) $1500
- — Z (S) $2000
1926.405 B01
- Issued
- Mar 26, 2014
- Abate by
- Apr 3, 2014
- Penalty
- Initial $2,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed: Guilford Mill Building, Panel T4 - The two receptacle outlet boxes were missing three knockouts.
Recent events (2)
- — I (S) $1500
- — Z (S) $2000
1926.405 B02
- Issued
- Mar 26, 2014
- Abate by
- Apr 3, 2014
- Penalty
- Initial $2,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.405(b)(2): In an energized installation, each outlet box did not have a cover, faceplate, or fixture canopy: Guilford Mill Building, Panel T4 - The two receptacle outlet boxes were not provided with covers.
Recent events (2)
- — I (S) $1500
- — Z (S) $2000
1926.405 D
- Issued
- Mar 26, 2014
- Abate by
- Apr 3, 2014
- Penalty
- Initial $2,000 · Current $1,500 Reduced
General-duty citation text
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front: Guilford Mill Building, Panel T4 - The panelboard, containing Square D breakers, was not dead front.
Recent events (2)
- — I (S) $1500
- — Z (S) $2000
More inspections at Border Electric, INC.
View Border Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in ME
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339645194.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.