Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BORDER ELECTRIC, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of BORDER ELECTRIC, INC. in ROUTE 190, EASTPORT, ME 04631 (NAICS 238210). OSHA activity number 339645194.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Border Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Border Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
ROUTE 190
City
EASTPORT
State
ME
ZIP
04631
Mailing
337 NORTH STREET, CALAIS, ME 04619
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

5 citations on file for this inspection.

1926.403 D01

Serious Gravity 5 2 instances 3 exposed
Issued
Mar 26, 2014
Abate by
Apr 3, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.403(d)(1): Electric equipment was not firmly secured to the surface on which it was mounted:  Guilford Mill Building, Panel T4 - The two receptacle outlet boxes and cable were not firmly secured.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

1926.404 E01 I

Serious Gravity 5 3 instances 3 exposed
Issued
Mar 26, 2014
Abate by
Apr 3, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.404(e)(1)(i): Conductors and equipment rated 600 volts, nominal, or less were not protected from overcurrent in accordance with their ability to safely conduct current:  Guilford Mill Building, Panel T4 - The 12 gauge conductors and receptacle outlets, rated for 20 amps, were connected to 50 amp breakers.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

1926.405 B01

Serious Gravity 5 3 instances 3 exposed
Issued
Mar 26, 2014
Abate by
Apr 3, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:   Guilford Mill Building, Panel T4 - The two receptacle outlet boxes were missing three knockouts.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

1926.405 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Mar 26, 2014
Abate by
Apr 3, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.405(b)(2): In an energized installation, each outlet box did not have a cover, faceplate, or fixture canopy:  Guilford Mill Building, Panel T4 - The two receptacle outlet boxes were not provided with covers.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

1926.405 D

Serious Gravity 5 1 instance 3 exposed
Issued
Mar 26, 2014
Abate by
Apr 3, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:   Guilford Mill Building, Panel T4 - The panelboard, containing Square D breakers, was not dead front.
Recent events (2)
  • — I (S) $1500
  • — Z (S) $2000

View Border Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339645194.