KITTERY, ME —
OSHA Inspection: NAVFAC PORTSMOUTH NAVAL SHIPYARD
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of NAVFAC PORTSMOUTH NAVAL SHIPYARD in BUILDING 154, KITTERY, ME 03904 (NAICS 811111). OSHA activity number 339646754.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVFAC PORTSMOUTH NAVAL SHIPYARD
- Site address
- BUILDING 154
- City
- KITTERY
- State
- ME
- ZIP
- 03904
- Mailing
- COMMANDING OFFICER NAVFAC MIDLANT (BLDG A81) 9742 MARYLAND AVE, NORFOLK, VA 23511
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811111
- Employees
- 185
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.24 F
- Issued
- May 8, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.24(f): Rise height and tread width were not uniform throughout any flight of stairs including any foundation structure used as one or more treads of the stairs: Location: Stairs to Mezzanine - On or about March 24, 2014, employees were exposed to a tripping hazard due to the difference of 4.75 inches between the height of the first step and the next step.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.101 B
- Issued
- May 8, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Location: Supply Room - On or about March 24, 2014, employees were exposed to projectile hazards from unsecured gas cylinders, two acetylene and one oxygen cylinder were not secured to prevent falling over.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 C01
- Issued
- May 8, 2014
- Abate by
- May 16, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: (a) Location: Tractor Bay - On or about March 24, 2014, three chemical fire extinguishers were located by the steel column in the middle of the room. Two of the extinguishers were not mounted and no signs was located above the extinguishers. (b) Location: Second floor - On or about March 24, 2014, one water fire extinguisher was located to the left of the stairs, it was not mounted and had no identifying signs. (c) Location: Tool area - On or about March 24, 2014, one chemical fire extinguisher was sitting on the floor (not mounted) and there was no sign. (d) Location: Outside of storage room - On or about March 24, 2014, the fire extinguisher was blocked by a saw.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 E03
- Issued
- May 8, 2014
- Abate by
- May 16, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: a) Location: Tractor bay - On or about March 24, 2014, two fire extinguishers on the steel column in the middle of the bay were last inspected in 2011. b) Location: Equipment Room - On or about March 24, 2014, a fire extinguisher located in the quipment room was last inspected in 2011.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.253 B04 III
- Issued
- May 8, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: Location: Supply room - On or about March 24, 2014, employees were exposed to increase risk of fire hazard due to two tanks of acetylene being stored with one tank of oxygen.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 G01 I
- Issued
- May 8, 2014
- Abate by
- May 15, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i): Work space was less than 30 inches wide in front of electric equipment operating at 600 volts, nominal, or less: (a) Location: Tractor Bay - On or about March 24, 2014, employees were exposed to increased risk of electrical shock from being unable to shut off the power as various items including a couch and a table, were located in front of electrical equipment. (b) Location: Main Bay - On or about March 24, 2014, employees were exposed to increased risk of electrical shock from being unable to shut off the power as large pieces of equipment were blocking access to electrical equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- May 8, 2014
- Abate by
- May 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Location: Main Bay - On or about March 24, 2014, employees were exposed to increased risk of electrical shock due to working near two electrical boxes had holes in the side that exposed the electrical wiring.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.1025 H01
- Issued
- May 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $0 · Current $0
15911592
General-duty citation text
29 CFR 1910.1025(h)(1): All surfaces were not maintained as free as practicable of accumulations of lead: Location: All Bays - On or about March 24, 2014, employees surfaces were not kept as free as practicable from accumulations of lead.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1025 H02 II
- Issued
- May 8, 2014
- Abate by
- Jun 4, 2014
- Penalty
- Initial $0 · Current $0
15911592
General-duty citation text
29 CFR 1910.1025(h)(2)(ii): Shoveling, sweeping or brushing methods were used to remove lead accumulations where vacuuming or other equally effective methods were available and feasible: Location: All Bays - On or about March 24, 2014, employees were required to dry sweep lead containing paint chips which has the potential to create an airborne lead hazard.