OSHA Inspection: TEAM ELECTRIC INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of TEAM ELECTRIC INC. in 6 PLATT STREET, NEW YORK, NY 10038 (NAICS 238210). OSHA activity number 339647448.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Team Electric INC. — free Get an email when a new federal OSHA severe-injury report for Team Electric INC. is published. One employer, no account, unsubscribe in one click.
Establishment
TEAM ELECTRIC INC.
Site address
6 PLATT STREET
City
NEW YORK
State
NY
ZIP
10038
Mailing
20 W 36TH ST #702, NEW YORK, NY 10018
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
13
Ownership type
A

5 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 10 63 instances 13 exposed
Issued
Apr 10, 2014
Abate by
Apr 16, 2014
Penalty
Initial $2,800 · Current $1,900 Reduced
29 CFR 1926.403(i)(2)(i): Employer did not ensure live parts of electric equipment operating at 50 volts or more were guarded against accidental contact by cabinets or other forms of enclosures.     (a) 6 Platt Street, Every Floor by Elevator Lobby.      Employees working on the 10th and 21st floor were not protected from electric shock by accidental contact with energized parts in load centers.  Circuit breakers parts and bus bars were exposed because covers had not been installed on the energized panel boxes.      NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1900
  • — Z (S) $2800

1926.405 A02 II E

Serious Gravity 5 12 instances 13 exposed
Issued
Apr 10, 2014
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1926.405(a)(2)(ii)(E): Employer did not ensure lamps used in temporary wiring for general illumination were protected from accidental contact or breakage:    (a) 6 Platt Street, New York, NY throughout building floors 10 through 20.    Employees working throughout building were not protected from electric shock or burns from accidental contact with broken or exposed lamp sockets. Numerous temorary lamp sockets in hallways and rooms were not protected with a protective cover or cage.    NOTE:  BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASE FILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION OR DOCUMENTATION OF ABATEMENT OF THIS VIOLATION AS NORMALLY REQUIRED BY 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1926.405 A02 II F

Serious Gravity 5 20 instances 13 exposed
Issued
Apr 10, 2014
Abate by
Apr 22, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(F): Employer did not ensure Temporary lights were not suspended by their electric cords unless cords and lights are designed for this means of suspension.  a)  6 Platt Street, New Yrok, NY numerous locations throughout project.  Temporary lights for general illumination were installed on the walls of the hallways mounted about 6 feet above the floor. The temporary lights were suspended by their electric wires and not provided with any strain relief.  NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B02

Serious Gravity 5 1 instance 13 exposed
Issued
Apr 10, 2014
Penalty
Initial $2,000 · Current $1,950 Reduced
29 CFR 1926.405(b)(2): Covers and canopies. All pull boxes, junction boxes, and fittings shall be provided with covers. If metal covers are used, they shall be grounded. In energized installations each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear.    (a) 6 Platt Street, 10 th floor outside elevator lobby.     Employees working in hallways outside elevator lobby were exposed to electrical shocks due to an branch circuit wire running not being installed in junctoin boxes with covers.     NOTE:  BECAUSE ABATEMENT OF THIS VIOLATION IS ALREADY DOCUMENTED IN THE CASE FILE, THE EMPLOYER NEED NOT SUBMIT CERTIFICATION OR DOCUMENTATION OF ABATEMENT OF THIS VIOLATION AS NORMALLY REQUIRED BY 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1950
  • — Z (S) $2000

1926.405 J01 I

Serious Gravity 10 10 instances 13 exposed
Issued
Apr 10, 2014
Abate by
Apr 16, 2014
Penalty
Initial $2,800 · Current $0 Reduced
29 CFR 1926.405(j)(1)(i): Employer did not ensure Fixtures, lampholders, lamps, rosettes, and receptacles have no live parts normally exposed to employee contact.     a).  6 Platt Street, New York, NY, 10th floor.    Employees working throughout the building on energized electric wires, were installing or relocating switch and outlet devices at entry halls to individual rooms and were exposed to elctric shock or burns because the devices were not properly secured to the junction boxes.    NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1,000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2800

View Team Electric INC.'s full OSHA safety record →