OSHA Inspection: FLINT HILLS RESOURCES FAIRMONT, L.L.C.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FLINT HILLS RESOURCES FAIRMONT, L.L.C. in 1214 RD. G, FAIRMONT, NE 68354 (NAICS 325193). OSHA activity number 339652349.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Flint Hills Resources Fairmont, L.L.C. for free Get an email when a new federal OSHA severe-injury report for Flint Hills Resources Fairmont, L.L.C. is published. One employer, no account, unsubscribe in one click.
Site address
1214 RD. G
City
FAIRMONT
State
NE
ZIP
68354
Mailing
1214 RD. G, FAIRMONT, NE 68354
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325193
Employees
54
Ownership type
A

4 citations on file for this inspection.

1910.119 E03 VII

Serious Gravity 5 1 instance 8 exposed
Issued
Aug 15, 2014
Abate by
Sep 19, 2014
Penalty
Initial $3,825 · Current $2,678 Reduced
29 CFR 1910.119(e)(3)(vii): The employer did not ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls:     1214 Road G, Fairmont, NE 68354: The employer is failing to ensure that the process hazard analysis (PHA) had a complete qualitative evaluation of a range of the possible safety and health effects of failures of controls. The process hazard analysis (PHA) was completed on April 26, 2012. However, the PHA did not fully address qualitative evaluation of a range of the possible safety and health effects of failures of controls including, but not limited to; having an incomplete evaluation on the PHA  Unit: Ammonia Unloading. There was an evaluation of the unloading of the wrong material; however, the consequences in regard to the possible injury did not detail what the actual injuries could be.    Abatement certification is required for this violation.  The abatement certification sheet is enclosed with the citations.
Recent events (2)
  • · I (S) $2677.5
  • · Z (S) $3825

1910.303 F02

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 15, 2014
Penalty
Initial $3,825 · Current $2,678 Reduced
29 CFR 1910.303(f)(2):  Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose:    11214 Road G, Fairmont, NE 68354 (Maintenance Room): The employer is failing to ensure that electrical disconnect devices were legibly marked to indicate their purpose. There were disconnects in an electrical box that did not have identification for any of them.
Recent events (2)
  • · I (S) $2677.5
  • · Z (S) $3825

1910.303 G01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 15, 2014
Penalty
Initial $3,825 · Current $2,678 Reduced
29 CFR 1910.303(g)(1)(ii):  Working space about electric equipment rated 600 volts, nominal, or less was used for storage:    1214 Road G, Fairmont, NE 68354 (Maintenance Room): The employer is failing to ensure that the working space in front of electrical equipment was not used for storage. There is a container of lubricant stored in front of an electrical disconnect rated at 120/208 volts.
Recent events (2)
  • · I (S) $2677.5
  • · Z (S) $3825

1910.157 E03

Other-than-serious 2 instances 2 exposed
Issued
Aug 15, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3):  Portable fire extinguishers were not subjected to an annual maintenance check:    1214 Road G, Fairmont, NE 68354 (Maintenance Room): The employer is failing to ensure that all portable fire extinguishers were checked annually. The last time that two carbon dioxide portable fire extinguishers in the maintenance department were checked was in 2012.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339652349.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.