PLYMOUTH, CT —
OSHA Inspection: FJC SERVICES, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of FJC SERVICES, LLC in 15 CONTAINER DRIVE, PLYMOUTH, CT 06782 (NAICS 332813). OSHA activity number 339658726.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FJC SERVICES, LLC
- Site address
- 15 CONTAINER DRIVE
- City
- PLYMOUTH
- State
- CT
- ZIP
- 06782
- Mailing
- P.O. BOX 8, PLYMOUTH, CT 06782
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332813
- Employees
- 8
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.37 A03
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $1,200 · Current $600 Reduced
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: A. On or about April 3, 2014, Emergency Exit Near Utica Boiler: The exit route from the emergency exit into the courtyard was blocked by a 6-inch corrugated plastic pipe used to divert heavy rain from the area.
Recent events (2)
- — I (S) $600
- — Z (S) $1200
1910.179 G01 V
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not constructed to prevent electrical shock and were not clearly marked for identification of functions: A. On or about April 3, 2014, Centrifuge area: The pendant control for the CM Shopstar hoist had a crack in the housing, exposing employees to electric shock hazards. The control was wrapped with black electrical tape which obscured the identification of the control buttons.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.219 F03
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven (7) feet or less above floors or platforms were not enclosed: A. On or about April 3, 2014, in the following locations, unguarded chains and sprockets exposed employees to amputation hazards: 1. ODD Dryer 2. Passivation Line, Basket Rotator #3 3. Passivation Line, Basket Rotator #4
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1910.303 B02
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: A. On or about April 3, 2014: 1. Passivation Area Drying Table: A Belkin 6-receptacle relocatable power tap was energized through an extension cord, against listing and labeling instructions. The receptacles provided power to the Dayton blower fan and Haulmaster electric hoist. 2. At Donaldson Torit VS-1500 Dust Collector: A Ridgid 16-Gallon Professional Wet/Dry Vac, WD19560, S/N 12335R0297 was used on a monthly basis to clean accumulated combustible cob dust from the collection drawer of the dust collector unit, against the manufacturer's instructions.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.305 B01 I
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: A. On or about April 3, 2014, Shop: The Honeywell power supply box on the Utica Boiler was missing a knockout, exposing employees to electric shock hazards.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.305 B01 II
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: A. On or about April 3, 2014, Electrical Panel "C": An unused opening in the panel was not covered by a breaker or blank, exposing employees to electric shock hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: A. On or about April 3, 2014, Passivation Area: In the following instances, flexible cords were used as a substitute for the fixed wiring of the building: 1. A yellow extension cord was used to power a Belkin 6-receptacle relocatable power tap which in turn powered a Dayton blower fan and HaulMaster electric hoist. 2. A blue extension cord was used to power the control panel at the Ogden dryer.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
1910.305 G01 IV D
- Issued
- Oct 3, 2014
- Abate by
- Nov 21, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: A. On or about April 3, 2014, Passivation Area: In the following instances, flexible cords were attached to building surfaces: 1. A yellow extension cord was attached to the structure of the building and strewn over a light fixture. The cord was used to power a Belkin 6-receptacle relocatable power tap which in turn powered a Dayton blower fan and HaulMaster electric hoist. 2. A blue extension cord was attached to the structure of the building and strewn over a light fixture. The cord was used to power the control panel at the Ogden dryer.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at FJC Services, LLC
View FJC Services, LLC's full OSHA safety record →
More inspections in this industry (NAICS 332813)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339658726.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.