Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: BUCHHEIT INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUCHHEIT INC in 1011 S. PERRYVILLE BLVD., PERRYVILLE, MO 63775 (NAICS 423310). OSHA activity number 339660748.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Buchheit INC for free Get an email when a new federal OSHA severe-injury report for Buchheit INC is published. One employer, no account, unsubscribe in one click.
Establishment
BUCHHEIT INC
Site address
1011 S. PERRYVILLE BLVD.
City
PERRYVILLE
State
MO
ZIP
63775
Mailing
33 PCR 540, PERRYVILLE, MO 63775
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423310
Employees
61
Ownership type
Private (A)

7 citations on file for this inspection.

1910.23 D01 II

Serious Gravity 1 1 instance 4 exposed
Issued
Apr 11, 2014
Abate by
May 29, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.23(d)(1)(ii): Stairway(s) less than 44 inches wide having one side open, did not have at least one stair railing on the open side:    a. In the yard storage building, the stair/hand rail to the second floor was in disrepair; nails were pulled loose and the rail was not secure at the bottom and top of the rail (only attached in the middle).     Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • · I (S) $1377
  • · Z (S) $2295

1910.157 G02

Serious Gravity 1 1 instance 61 exposed
Issued
Apr 11, 2014
Abate by
May 29, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter:    a. Where employees were initially trained on the use of portable fire extinguishers for incipient stage fires, annual training was not provided.  (Note: abatement could include limiting who would use extinguishers, and/or establishing an evacuation program and prohibiting the use of extinguishers by employees.)     Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • · I (S) $1377
  • · Z (S) $2295

1910.157 C01

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 11, 2014
Abate by
May 29, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a. A portable fire extinguisher was blocked by pallets and stacks of merchandise in the store storage area.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 11, 2014
Abate by
May 29, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a. The disconnect to the battery charger in the storage area was mounted on a wall blocked by steel racking; pallets and stacks of merchandise in front of the racking added to the blocking of the disconnect.  Abatement certification and abatement documentation is required for this violation.  The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful.  The abatement certification sheet is enclosed with the citation(s).
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.212 A03 II

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 11, 2014
Penalty
Initial $3,825 · Current $2,295 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    a. The guard was missing from the abrasive wheel cut-off saw, used for cutting rebar.
Recent events (2)
  • · I (S) $2295
  • · Z (S) $3825

1910.334 A02 II

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 11, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:  a. The power cord was damaged, with exposed conductors, to the abrasive wheel cut-off saw, used for cutting rebar.  b. The power cord was damaged, with exposed conductors, to the panel saw, used for cutting wood panels such as pegboard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.334 A03 I

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 11, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor:  a. The ground pin was missing from the abrasive wheel cut-off saw power cord, used for cutting rebar.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

View Buchheit INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339660748.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.