Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,197,549Inspections Most recent open 2026-08-27 Last loaded 2026-08-31

OSHA Inspection: VETERANS AFFAIRS SEATTLE REGIONAL OFFICE SEATAC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of VETERANS AFFAIRS SEATTLE REGIONAL OFFICE SEATAC in 17930 PACIFIC HIGHWAY SOUTH, SEATAC, WA 98188 (NAICS 923140). OSHA activity number 339662975.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Veterans Affairs Seattle Regional Office Seatac for free Get an email when a new federal OSHA severe-injury report for Veterans Affairs Seattle Regional Office Seatac is published. One employer, no account, unsubscribe in one click.
Site address
17930 PACIFIC HIGHWAY SOUTH
City
SEATAC
State
WA
ZIP
98188
Mailing
915 SECOND AVENUE ROOM 1086, SEATTLE, WA 98174
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
923140
Employees
280
Ownership type
Federal government (D)

4 citations on file for this inspection.

1910.303 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 15, 2014
Abate by
May 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:  a)     SE Corner Plaza, Voice and Data #13;  Cubicle wiring, which should have been enclosed, was exposed and bare copper wiring was showing, exposing employees to possible electrical shock hazards.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Repeat Gravity 5 3 instances 6 exposed
Issued
Apr 15, 2014
Abate by
May 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a)  2nd Floor, Cubicle 2T4;  A fan was plugged into a brown extension cord, violating the extension cords UL listing and labeling for temporary use.  This exposes employees to possible electrical fire hazards.    (b)  Plaza Level, Cubicle P30; A Pelonis heater was plugged into a relocatable power tap.  The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.    (c)  4th Floor, Cubicle 4B4;  A small purple heater was plugged into a relocatable power tap. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.    The Veterans Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 928064 citation 1, item 2, issued on August 27, 2013 with respect to a workplace at Reno, NV.    The Veterans Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 779683 citation 1, item 1, issued on December 26, 2012 with respect to a workplace at Seattle, Washington.    The Veterans Administration was previously cited for a violation of this standard which was contained in OSHA inspection no. 779641 citation 1, item 1, issued on December 26, 2012 with respect to a workplace at Seattle, Washington.
Recent events (1)
  • · Z (R) $0

1910.36 G02

Other-than-serious 1 instance 1 exposed
Issued
Apr 15, 2014
Abate by
May 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:  a)     3rd Floor, Cubicle 3Y4;  There was a 24 inch aisleway between a cubicle wall and the wall.
Recent events (1)
  • · Z (O) $0

1910.157 E02

Other-than-serious 1 instance 20 exposed
Issued
Apr 15, 2014
Abate by
May 18, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  a)     All Amerex fire extinguishers on the lower plaza, plaza, 2nd, 3rd and 4th floor had not been inspected monthly.
Recent events (1)
  • · Z (O) $0

View Veterans Affairs Seattle Regional Office Seatac's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339662975.