Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: S & T MANUFACTURING

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of S & T MANUFACTURING in 17411 E. PINE ST., TULSA, OK 74116 (NAICS 332312). OSHA activity number 339665945.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch S & T Manufacturing — free Get an email when a new federal OSHA severe-injury report for S & T Manufacturing is published. One employer, no account, unsubscribe in one click.
Establishment
S & T MANUFACTURING
Site address
17411 E. PINE ST.
City
TULSA
State
OK
ZIP
74116
Mailing
17411 E. PINE ST., TULSA, OK 74116
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
120
Ownership type
A

6 citations on file for this inspection.

1910.37 A03

Serious Gravity 1 1 instance 15 exposed
Issued
May 2, 2014
Abate by
May 12, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:     On or about March 4, 2014, and at times prior thereto, in the welding shop areas a fire exit door was obstructed by vending machines. This would slow down exit discharge in case of fire exposing employees to fire hazards.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295

1910.37 B02

Serious Gravity 1 1 instance 15 exposed
Issued
May 2, 2014
Abate by
May 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":      On or about March 4, 2014, and at times prior thereto, in the one of the maintenance shops and welding shops fire exit doors were not marked with a sign reading "Exit". This hinders employees finding an exit in case of fire, exposing employees to a fire hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 E06 II

Serious Gravity 1 1 instance 5 exposed
Issued
May 2, 2014
Abate by
May 12, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.106(e)(6)(ii): Class I flammable liquid(s) were dispensed into containers, vehicles, and equipment without electrically interconnecting the nozzle and the container, vehicles, or equipment:          On or about March 3, 2014, and at times prior thereto, in the paint areas lacquer thinner having flashpoint of 18 degrees F was dispensed into a smaller container without being effectively grounded and bonded to electrically interconnect the containers to prevent static discharge during dispensing operation, exposing employees to a fire hazard.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295

1910.107 G05

Serious Gravity 1 1 instance 5 exposed
Issued
May 2, 2014
Abate by
Jun 17, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.107(g)(5): The use of solvents for cleaning operations was not restricted to those having flashpoints not less than 100 degrees F or the solvents having flashpoints not less than those normally used in the spray operation:        On or about April 3, 2014, and at times prior thereto, in the paint areas employees were using lacquer thinner having flashpoint of 18 degrees F as a solvent for cleaning operations. This exposes employees to fire hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 G01 V

Serious Gravity 1 1 instance 15 exposed
Issued
May 2, 2014
Abate by
May 19, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not constructed to prevent electrical shock:     On or about April 3, 2014, and at times prior thereto, in the crane area of paint building an overhead crane pendant control box was observed having control button missing exposing live voltage. The employees were exposed to electric shock hazard.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295

1910.253 B04 III

Serious Gravity 1 1 instance 15 exposed
Issued
May 2, 2014
Abate by
May 12, 2014
Penalty
Initial $2,295 · Current $1,377 Reduced
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour:     On or about April 4, 2014, and at times prior thereto, at the compressed air cylinders storage area outside the Miratech weld shop oxygen, acetylene and propane cylinders were found stored together without a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour or separated a minimum distance of 20 feet. Employees were exposed to the hazard of fire.
Recent events (2)
  • — I (S) $1377
  • — Z (S) $2295

View S & T Manufacturing's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339665945.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.