DUBUQUE, IA ·
OSHA Inspection: SUNFLOWER ENTERPRISES, L.L.C.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of SUNFLOWER ENTERPRISES, L.L.C. in 5 JONES STREET, DUBUQUE, IA 52001 (NAICS 336611). OSHA activity number 339672958.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUNFLOWER ENTERPRISES, L.L.C.
- Site address
- 5 JONES STREET
- City
- DUBUQUE
- State
- IA
- ZIP
- 52001
- Mailing
- 5 JONES STREET, DUBUQUE, IA 52001
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336611
- Employees
- 8
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1910.304 B04 II B
- Issued
- Jul 11, 2014
- Penalty
- Initial $1,700 · Current $500 Reduced
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4: (a) In the break room area, the Magic Chef microwave operating at 1.5 kilowatts was plugged into a 15 amp Relocatable Power Tap (RPT) rated for 12 amps. Also, plugged into the RPT was a a Crosley Refrigerator operated at 4.5 amps and computer equipment (i.e. monitor, printer) operated at approximately 60 watts and chargers, thereby exceeding the rated capacity of the RPT which overloaded the relocatable power tap and the receptacle.
Recent events (2)
- · I (S) $500
- · Z (S) $1700
1910.305 A02 IX
- Issued
- Jul 11, 2014
- Penalty
- Initial $1,600 · Current $500 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(ix): Lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard (a) In the weld shop, a lamp for added general illumination did not have a suitable guard to protect workers from accidental contact or breakage.
Recent events (2)
- · I (S) $500
- · Z (S) $1600
More inspections in this industry (NAICS 336611)
More inspections in IA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339672958.