LUBBOCK, TX ·
OSHA Inspection: PARK TOWER APARTMENTS
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of PARK TOWER APARTMENTS in 1617 27TH STREET, SUITE 110, LUBBOCK, TX 79411 (NAICS 531110). OSHA activity number 339673089.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PARK TOWER APARTMENTS
- Site address
- 1617 27TH STREET, SUITE 110
- City
- LUBBOCK
- State
- TX
- ZIP
- 79411
- Mailing
- 1617 27TH STREET, SUITE 110, LUBBOCK, TX 79411
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- Yes
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 531110
- Employees
- 6
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.303 H05 III B
- Issued
- Aug 14, 2014
- Abate by
- Aug 26, 2014
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.303(h)(5)(iii)(B): Permanent and conspicuous warning signs were not provided, reading substantially as follows: "DANGER -- HIGH VOLTAGE -- KEEP OUT." On or about April 10, 2014 employees were exposed to contact with live electrical parts because entrances to high voltage transformer closets did not have danger signs warning of high voltage in the following instances: a) 3rd floor transformer room b) 6th floor transformer room c) 9th floor transformer room d) 12th floor transformer room
Recent events (3)
- · J (S) $2500
- · C (S) $5000
- · Z (S) $5000
1910.332 B01
- Issued
- Aug 14, 2014
- Abate by
- Aug 26, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments: On or about April 10, 2014 employees were exposed to electrical hazards while installing Cat 5 cabling within energized transformer closets on floors 3, 6, 9 and 12. The employees had not been trained to de-energize and lockout energized electrical equipment and circuit parts.
Recent events (3)
- · J (S) $3500
- · C (S) $7000
- · Z (S) $7000
1910.333 A01
- Issued
- Aug 14, 2014
- Abate by
- Aug 26, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee could be exposed was not de-energized before the employee worked on or near them: On or about April 10, 2014, employees were exposed to electrical hazards while performing work in close proximity to an energized electrical transformer and its live circuit parts.
Recent events (3)
- · J (S) $3500
- · C (S) $7000
- · Z (S) $7000
1910.335 A01 I
- Issued
- Aug 14, 2014
- Abate by
- Aug 26, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On or about April 10, 2014, employees were exposed to electrical hazards and were not provided with personal protective equipment, including but not limited to flame resistant clothing, hand protection, face and head area protection, and hearing protection, appropriate for the work being performed on floors 3, 6, 9 and 12.
Recent events (3)
- · J (S) $3500
- · C (S) $7000
- · Z (S) $7000
1910.335 A02 I
- Issued
- Aug 14, 2014
- Abate by
- Aug 26, 2014
- Penalty
- Initial $5,000 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts: On or about April 10, 2014, employees were exposed to electrical hazards while using a non-insulated metal fishing tool to pull category five cabling between floors and through walls.
Recent events (3)
- · J (S) $2500
- · C (S) $5000
- · Z (S) $5000
More inspections at Park Tower Apartments
View Park Tower Apartments's full OSHA safety record →
More inspections in this industry (NAICS 531110)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339673089.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.