Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,195,903Inspections Most recent open 2026-08-18 Last loaded 2026-08-21

OSHA Inspection: EASTHAM ENTERPRISES INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of EASTHAM ENTERPRISES INC. in 2.7 MILES S. OF PECOS, RIG #1, CITY OF PECOS 13 LEASE, WELL #3H, PECOS, TX 79772 (NAICS 213111). OSHA activity number 339675787.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Eastham Enterprises INC. for free Get an email when a new federal OSHA severe-injury report for Eastham Enterprises INC. is published. One employer, no account, unsubscribe in one click.
Site address
2.7 MILES S. OF PECOS, RIG #1, CITY OF PECOS 13 LEASE, WELL #3H
City
PECOS
State
TX
ZIP
79772
Mailing
4710 BELLAIRE BLVD. SUITE 350, BELLAIRE, TX 77401
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
12
Ownership type
Private (A)

4 citations on file for this inspection.

1910.22 B01

Serious Gravity 1 3 instances 12 exposed
Issued
May 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $2,295 · Current $1,600 Reduced
29 CFR 1910.22(b)(1): Aisles and passageways were not kept clear and in good repair, with no obstruction across or in aisles that could create a hazard:    On or about April 14, 2014, Rig #1, passageways were not kept clear and in good repair. Employees were exposed to trip hazards in the following instances:          1)    On the rig floor, the stairway landing leading up from the mud pumps stuck up approximately 1 to 2              inches above the tank floor and was not flush with the floor.       2)    On the rig floor, the stairway landing leading up from the pipe landing stuck up approximately 1 to 2              inches above the tank floor and was not flush with the floor.      3)    A four-inch water hose at the water tank ran across the path of the stairway crew creating a trip hazard.
Recent events (2)
  • · I (S) $1600
  • · Z (S) $2295

1910.305 A02 X

Serious Gravity 10 1 instance 1 exposed
Issued
May 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $6,300 · Current $3,000 Reduced
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points:    On or about April 14, 2014, Rig #1, a 480V nominal electrical cable used to supply power to the air compressor that controls the active mud tank(s) was pinched between the doors of a metal suitcase where the rigs electrical cables were housed. Employees were exposed electrical shock hazards.
Recent events (2)
  • · I (S) $3000
  • · Z (S) $6300

1910.303 F02

Other-than-serious 1 instance 12 exposed
Issued
May 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    On or about April 14, 2014, Rig #1, behind the Drillers House, the circuits inside the circuit breaker box were not legibly marked to indicate their purpose, Employees were exposed to electrical shock hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.305 G01 IV B

Other-than-serious 3 instances 12 exposed
Issued
May 14, 2014
Abate by
Jun 4, 2014
Penalty
Initial $765 · Current $400 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:    On or about April 14, 2014, Rig #1, 110V and 480V nominal electrical cables were run through holes in walls. Employees were exposed to electrical shock hazards in the following instances:          1)    In the Change House, an 110V nominal electrical cable used to power the flood light outside the change house               was run through a hole in the metal wall.      2)    In the Top Doghouse, two 110V nominal electrical cables used to power the lights inside and outside of the               doghouse were run through holes in the metal wall.      3)    At the Active Mud Tanks, three 480V nominal electrical cables were run through metal piping with protection               such as bushings.
Recent events (2)
  • · I (O) $400
  • · Z (O) $765

View Eastham Enterprises INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339675787.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.