Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNICOLD CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of UNICOLD CORPORATION in 3140 UALENA STREET, HONOLULU, HI 96819 (NAICS 493120). OSHA activity number 339676553.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Unicold Corporation — free Get an email when a new federal OSHA severe-injury report for Unicold Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
UNICOLD CORPORATION
Site address
3140 UALENA STREET
City
HONOLULU
State
HI
ZIP
96819
Mailing
3140 UALENA STREET, HONOLULU, HI 96819
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
50
Ownership type
A

2 citations on file for this inspection.

1910.119 F03

Serious Gravity 5 2 instances 50 exposed
Issued
Jun 27, 2014
Abate by
Aug 1, 2014
Penalty
Initial $3,500 · Current $2,275 Reduced
29 CFR 1910.119(f)(3): The operating procedures were not reviewed as often as necessary to assure that they reflect current operating practice, including changes that result from changes in process chemicals, technology, and equipment, and changes to facilities.      a) On or about April 25, 2014, the written standard operating procedure for "Major Ammonia Leak" did not reflect current operating practice as it only instructed for managers and personnel to assemble at the Ualena Street Gate, and did not make reference to choosing an assembly point based upon wind direction.      b) On or about April 25, 2014, the written standard operating procedure for "General Procedure for Ammonia Leak" did not reflect current operating practice as it did not contain steps to follow for emergency shutdown of the entire system.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

1910.119 J02

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 27, 2014
Abate by
Aug 1, 2014
Penalty
Initial $3,500 · Current $2,275 Reduced
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment.        a) On or about April 25, 2014, where written procedures were not established to maintain the on-going integrity of valves on the covered system, including stop (shut-off) valves.
Recent events (2)
  • — I (S) $2275
  • — Z (S) $3500

View Unicold Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339676553.