Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PIGOTT ELECTRIC CO., INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of PIGOTT ELECTRIC CO., INC. in 75 LEONARD STREET, BELMONT, MA 02478 (NAICS 238210). OSHA activity number 339695918.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pigott Electric CO., INC. — free Get an email when a new federal OSHA severe-injury report for Pigott Electric CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
75 LEONARD STREET
City
BELMONT
State
MA
ZIP
02478
Mailing
47 DUDLEY STREET, ARLINGTON, MA 02476
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
15
Ownership type
A

3 citations on file for this inspection.

1926.403 I02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 23, 2014
Penalty
Initial $1,500 · Current $1,050 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.  (a) Location - 75 Leonard Street, Belmont, MA: On or about 4/18/14, an employee was exposed to electrical hazards from a uncovered electrical box on the ceiling that was less than 8 feet high.
Recent events (2)
  • — I (S) $1050
  • — Z (S) $1500

1926.405 A02 II B

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 23, 2014
Penalty
Initial $1,200 · Current $840 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Runs of open conductors were not located where the conductors will not be subject to physical damage. The conductors were not fastened at intervals not exceeding 10 feet (3.05 m); with branch-circuit conductors laid upon the floor.   (a) Location - 75 Leonard Street, Belmont, MA: On or about 4/15/14, wiring used for temporary electric power were laid on the floor and subject to damage.
Recent events (2)
  • — I (S) $840
  • — Z (S) $1200

1926.403 B02

Other-than-serious 1 instance 4 exposed
Issued
Jun 23, 2014
Penalty
Initial $300 · Current $210 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  (a) LOCATION - 75 Leonard Street, Belmont, MA: On or about 4/15/14, electrical knockout boxes were used on the floor and not mounted and did not provide strain relief.
Recent events (2)
  • — I (O) $210
  • — Z (O) $300

View Pigott Electric CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339695918.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.