EL PASO, TX —
OSHA Inspection: THE HOME DEPOT USA INC. STORE 8523
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE HOME DEPOT USA INC. STORE 8523 in 12221 MONTWOOD DRIVE, EL PASO, TX 79936 (NAICS 444110). OSHA activity number 339738643.
Where did this inspection happen?
- Establishment
- THE HOME DEPOT USA INC. STORE 8523
- Site address
- 12221 MONTWOOD DRIVE
- City
- EL PASO
- State
- TX
- ZIP
- 79936
- Mailing
- 2455 PACES FERRY RD., ATLANTA, GA 30339
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 444110
- Employees
- 158
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.303 G01
- Issued
- Abate by
- Penalty
- Initial $2805.00 · Current $1950.00 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about April 22, 2014, and at times thereto, employer failed to maintain a clear area in front of the electrical panel located next to an exit door, in the air conditioner section. this condition exposed the employees to an electrical and fire hazard.
Recent events (2)
- — I (O) $1950
- — Z (S) $2805
1910.305 B01 II
- Issued
- Abate by
- Penalty
- Initial $4675.00 · Current $3290.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about April 22, 2014, and at times prior thereto, the employer did not place filler plates in the breaker box, located in the electrical room in the receiving area, exposing energized parts. This condition exposed the employees to electrical hazards.
Recent events (2)
- — I (S) $3290
- — Z (S) $4675
1910.305 B02 I
- Issued
- Abate by
- Penalty
- Initial $3740.00 · Current $2610.00 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about April 22, 2014, the electrical outlet boxes under the desk located in the managers office hallway were not covered. This condition exposed the employees to an electrical hazard.
Recent events (2)
- — I (S) $2610
- — Z (S) $3740
More inspections in this industry (NAICS 444110)
TACOMA, WA—2026-07-08
WA317991863 - LOWES HOME CENTERS LLC
HUNTSVILLE, AL—2026-06-30
THE HOME DEPOT U.S.A., INC.
RICHLAND, WA—2026-06-26
WA317991859 - HOME DEPOT INC THE
HENDERSONVILLE, TN—2026-06-26
84 LUMBER
FERNDALE, WA—2026-06-25
WA317991811 - BFS GROUP LLC
More inspections in TX
SPRING, TX—2026-07-10
DORSTENER WIRE TECH INC.
FORT WORTH, TX—2026-07-10
RC PROFESSIONAL ROOFING OF TEXAS LLC
CYPRESS, TX—2026-07-10
FEDERICO CARVAJAL GARCIA
SAN ANTONIO, TX—2026-07-10
ED LONG'S METAL WORKS
SAN ANTONIO, TX—2026-07-09
WAREHOUSE RACK COMPANY, LP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339738643.