TONAWANDA, NY —
OSHA Inspection: GAINES ELECTRICAL CONTRACTING, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of GAINES ELECTRICAL CONTRACTING, INC. in SHERIDAN PLAZA 2309 EGGERT ROAD, TONAWANDA, NY 14150 (NAICS 238210). OSHA activity number 339746018.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- GAINES ELECTRICAL CONTRACTING, INC.
- Site address
- SHERIDAN PLAZA 2309 EGGERT ROAD
- City
- TONAWANDA
- State
- NY
- ZIP
- 14150
- Mailing
- 4701 MILITARY ROAD, NIAGARA FALLS, NY 14305
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 2
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.403 B02
- Issued
- May 22, 2014
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) On or about 4/25/14, in the former Office Depot Store Construction site, Sheridan Plaza, 2309 Eggert Rd., Tonawanda, NY: An unsecured metal 4-receptacle outlet box was laying on the floor. A flexible cord spliced into wires hanging out of a junction box on the wall and running along the floor, was connected to the metal 4-receptacle outlet box, supplying 120 volt-ac power to the receptacles in the box. This set-up was installed by the Electrical Contractor to supply electrical power for use by contractors on the site. Article 370-13 of the National Electric Code requires the metal 4-receptacle outlet box to be rigidly and securely fastened in place. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — J (S) $0
- — C (S) $1200
- — Z (S) $1200
1926.405 B02
- Issued
- May 22, 2014
- Penalty
- Initial $1,200 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy: a) On or about 4/25/14, in the back portion of the former Office Depot Store Construction site, Sheridan Plaza, 2309 Eggert Rd., Tonawanda, NY: There was no faceplate on a 4-receptacle outlet box mounted in a wall. An employee plugged in a Milwaukee portable bandsaw into one of the receptacles, used the bandsaw to cut conduit, and then unplugged the saw. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
- — J (O) $0
- — C (S) $1200
- — Z (S) $1200
More inspections at Gaines Electrical Contracting, INC.
View Gaines Electrical Contracting, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339746018.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.