OSHA Inspection: GAINES ELECTRICAL CONTRACTING, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GAINES ELECTRICAL CONTRACTING, INC. in SHERIDAN PLAZA 2309 EGGERT ROAD, TONAWANDA, NY 14150 (NAICS 238210). OSHA activity number 339746018.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gaines Electrical Contracting, INC. — free Get an email when a new federal OSHA severe-injury report for Gaines Electrical Contracting, INC. is published. One employer, no account, unsubscribe in one click.
Site address
SHERIDAN PLAZA 2309 EGGERT ROAD
City
TONAWANDA
State
NY
ZIP
14150
Mailing
4701 MILITARY ROAD, NIAGARA FALLS, NY 14305
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
May 22, 2014
Penalty
Initial $1,200 · Current $0 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) On or about 4/25/14, in the former Office Depot Store Construction site, Sheridan Plaza, 2309 Eggert Rd., Tonawanda, NY: An unsecured metal 4-receptacle outlet box was laying on the floor. A flexible cord spliced into wires hanging out of a junction box on the wall and running along the floor, was connected to the metal 4-receptacle outlet box, supplying 120 volt-ac power to the receptacles in the box. This set-up was installed by the Electrical Contractor to supply electrical power for use by contractors on the site. Article 370-13 of the National Electric Code requires the metal 4-receptacle outlet box to be rigidly and securely fastened in place.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (S) $0
  • — C (S) $1200
  • — Z (S) $1200

1926.405 B02

Other-than-serious 1 instance 1 exposed
Issued
May 22, 2014
Penalty
Initial $1,200 · Current $0 Reduced
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:        a) On or about 4/25/14, in the back portion of the former Office Depot Store Construction site, Sheridan Plaza, 2309 Eggert Rd., Tonawanda, NY: There was no faceplate on a 4-receptacle outlet box mounted in a wall. An employee plugged in a Milwaukee portable bandsaw into one of the receptacles, used the bandsaw to cut conduit, and then unplugged the saw.        NO ABATEMENT CERTIFICATION REQUIRED
Recent events (3)
  • — J (O) $0
  • — C (S) $1200
  • — Z (S) $1200

View Gaines Electrical Contracting, INC.'s full OSHA safety record →