OMAHA, NE ·
OSHA Inspection: REY'S DRYWALL
Unprogrammed Related inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Related safety inspection of REY'S DRYWALL in 17889 CHICAGO STREET, OMAHA, NE 68118 (NAICS 238310). OSHA activity number 339758302.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- REY'S DRYWALL
- Site address
- 17889 CHICAGO STREET
- City
- OMAHA
- State
- NE
- ZIP
- 68118
- Mailing
- 2216 S 10TH STREET, OMAHA, NE 68108
What kind of inspection was it?
- Inspection type
- Unprogrammed Related (G)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238310
- Employees
- 4
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 I02 I
- Issued
- Jul 15, 2014
- Abate by
- Aug 15, 2014
- Penalty
- Initial $1,600 · Current $1,440 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. Worksite located at 17889 Chicago Street, Omaha, NE: In the North stair tower on the 1st level, there was a light string were the splice left exposed live parts operating at 120 volts. The splice was attempted using wire nuts and electrical tape but left the energized conductor exposed. Abatement certification is required for this violation. The abatement certification sheet is enclosed with the citations.
Recent events (2)
- · I (S) $1440
- · Z (S) $1600
1926.405 A02 II F
- Issued
- Jul 15, 2014
- Abate by
- Aug 15, 2014
- Penalty
- Initial $1,600 · Current $1,440 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension: Worksite located at 17889 Chicago Street, Omaha, NE: Temporary light fixtures installed on the 2nd floor were suspended by their cords. The fixtures are designed to be suspended from a loop located at the top of the unit. Abatement certification is required for this violation. The abatement certification sheet is enclosed with the citations.
Recent events (2)
- · I (S) $1440
- · Z (S) $1600
1926.405 G02 III
- Issued
- Jul 15, 2014
- Abate by
- Aug 15, 2014
- Penalty
- Initial $1,600 · Current $0 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iii): The repair splice in a hard service flexible cord No. 12 or larger did not retain the insulation, outer sheath properties, and usage characteristics of the cord which was being used: Worksite located at 17889 Chicago Street, Omaha, NE: At a number of locations throughout the structure (1st, 2nd, and 3rd floors), temporary lights strings were spliced without retaining the insulation and outer sheath properties or the cord. The insulation was stripped back and the wire was spliced using wire nuts. Abatement certification is required for this violation. The abatement certification sheet is enclosed with the citations.
Recent events (2)
- · I (S) $0
- · Z (S) $1600
More inspections in this industry (NAICS 238310)
More inspections in NE
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339758302.