Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: CLAY DEAN ELECTRIC, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of CLAY DEAN ELECTRIC, LLC in 801 S. CHERRY STREET, GLENDALE, CO 80246 (NAICS 238210). OSHA activity number 339771123.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Clay Dean Electric, LLC for free Get an email when a new federal OSHA severe-injury report for Clay Dean Electric, LLC is published. One employer, no account, unsubscribe in one click.
Site address
801 S. CHERRY STREET
City
GLENDALE
State
CO
ZIP
80246
Mailing
9209 E. WAGON WHEEL WAY, PARKER, CO 80138
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

3 citations on file for this inspection.

1926.405 A02 II I

Other-than-serious 1 instance 30 exposed
Issued
Sep 19, 2014
Penalty
Initial $1,020 · Current $1,020
29 CFR 1926.405(a)(2)(ii)(I): Flexible cords and cables used for temporary wiring were not protected from damage:     (a)Clay Dean Electric, LLC at 801 Cherry Street, Glendale, CO  80246: On and before May 15th, 2014, the two 240 volt outdoor electrical cables used to provide temporary electrical power to the general contractor jobsite trailer(s) were not protected against damage. The two electrical cables were placed along the gate opening used by vehicles entering and exiting the worksite. As a result, the two electrical cables were substantially flattened from vehicles driving over the cables.
Recent events (2)
  • · I (O) $1020
  • · Z (S) $1020

1926.405 E01

Other-than-serious 2 instances 20 exposed
Issued
Sep 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.405(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures:     (a)Clay Dean Electric, LLC at 801 Cherry Street, Glendale, CO  80246: On and before May 15th, 2014, the two 240 volt outdoor electrical junction boxes used to provide temporary electrical power to the general contractor trailer(s) were not equipped with appropriate strain relief fittings. The strain relief fittings were not rated for damp and/or wet applications. Condition allowed moisture and or water to enter electrical boxes.                 (b)Clay Dean Electric, LLC at 801 Cherry Street, Glendale, CO 80246: On and before May 15th, 2014, the 240 volt electrical junction box used to provide temporary electrical power to the general contractor trailer(s) was not rated for damp or wet locations. Condition allowed moisture and or water to enter the metal electrical box.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

1926.405 G02 IV

Other-than-serious 2 instances 30 exposed
Issued
Sep 19, 2014
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(2)(iv): Strain relief. Flexible cords shall be connected to devices and fittings so that strain relief is provided which will prevent pull from being directly transmitted to joints or terminal screws.     (a)Clay Dean Electric, LLC at 801 Cherry Street, Glendale, CO  80246: On and before May 15th, 2014, the two 240 volt outdoor electrical cable boxes used to provide temporary electrical power to the general contractor jobsite trailer(s) were missing appropriate strain relief fittings. The outer sheath on both cables did not pass into and through the strain relief fittings.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339771123.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.