Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SACHS ELECTRIC COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SACHS ELECTRIC COMPANY in 901 HOG HOLLOW ROAD, CHESTERFIELD, MO 63017 (NAICS 238210). OSHA activity number 339778243.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sachs Electric Company — free Get an email when a new federal OSHA severe-injury report for Sachs Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
901 HOG HOLLOW ROAD
City
CHESTERFIELD
State
MO
ZIP
63017
Mailing
P.O. BOX 96, SAINT LOUIS, MO 63166
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
1136
Ownership type
A

4 citations on file for this inspection.

1926.21 B02

Other-than-serious 1 instance 1 exposed
Issued
Jun 19, 2014
Abate by
Jul 1, 2014
Penalty
Initial $7,000 · Current $1,000 Reduced
29 CFR 1926.21(b)(2):     The employer shall instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $7000

1910.333 B02 I

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jun 19, 2014
Abate by
Jul 1, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.333(b)(2)(i):  The employer did not maintain a written copy of the procedures outlined in paragraph (b)(2) and make it available for inspection by employees and by the Assistant Secretary of Labor and his or her authorized representatives:  a/  At the Missouri American Water Co., specifically the CP3B Switchgear Unit to Plant #3, an arc flash occurred on or about 05/14/14.  The written procedure for the lockout/tagout of this switchgear unit was not prepared until after the arc flash occurred.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.333 B02 II B

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Jun 19, 2014
Abate by
Jul 1, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources. Control circuit devices, such as push buttons, selector switches, and interlocks, may not be used as the sole means for deenergizing circuits or equipment. Interlocks for electric equipment may not be used as a substitute for lockout and tagging procedures:  a/  At the Missouri American Water Co., specifically the CP3B Switchgear Unit to Plant #3, an arc flash occurred on or about 05/14/14.  The primary switch to the south bus was isolated from the unit.  The high service line stemming from the north bus and running to the rear of CP3B SG was not isolated.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

1910.333 B02 III A

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jun 19, 2014
Abate by
Jul 1, 2014
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag was not placed on each disconnecting means used to deenergize circuits and equipment on which work is to be performed, except as provided in paragraphs (b)(2)(iii)(C) and (b)(2)(iii)(E) of this section. The lock was not attached so as to prevent persons from operating the disconnecting means unless they resort to undue force or the use of tools:  a/  At the Missouri American Water Co., specifically the CP3B Switchgear Unit to Plant #3, an arc flash occurred on or about 05/14/14.  One authorized employee was not provided with or used a padlock, suitable tag, or the equivalent for the purpose of isolating the 4,160 volts entering into the CP3B Switchgear Unit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7000

View Sachs Electric Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339778243.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.