HORSHAM, PA —
OSHA Inspection: EDON CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of EDON CORPORATION in 1160 EASTON ROAD, HORSHAM, PA 19044 (NAICS 326199). OSHA activity number 339784399.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EDON CORPORATION
- Site address
- 1160 EASTON ROAD
- City
- HORSHAM
- State
- PA
- ZIP
- 19044
- Mailing
- 1160 EASTON ROAD, HORSHAM, PA 19044
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 30
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G02 I
- Issued
- Jul 24, 2014
- Abate by
- Aug 12, 2014
- Penalty
- Initial $2,380 · Current $1,785 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): (a) Production Workshop Area - on or about May 28, 2014, employees were activating a light switch that was located directly below an unguarded junction box which was its missing cover and was not properly guarded to prevent contact with the exposed live parts energized in excess of 50 volts AC.
Recent events (2)
- — I (S) $1785
- — Z (S) $2380
1910.147 C06 I
- Issued
- Jul 24, 2014
- Abate by
- Aug 12, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: (a) Production Workshop Area On or about May 28, 2014, an employee performed various duties in the production workshop area where lockout/tag out hardware is used, but at least an annual inspection of the energy control procedures are not conducted, exposing employees to injury.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Edon Corporation