LUXEMBURG, WI ·
OSHA Inspection: PACKERLAND WHEY PRODUCTS, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of PACKERLAND WHEY PRODUCTS, INC. in 407 4TH STREET, LUXEMBURG, WI 54217 (NAICS 311514). OSHA activity number 339787079.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PACKERLAND WHEY PRODUCTS, INC.
- Site address
- 407 4TH STREET
- City
- LUXEMBURG
- State
- WI
- ZIP
- 54217
- Mailing
- 407 4TH STREET, LUXEMBURG, WI 54217
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311514
- Employees
- 30
- Ownership type
- Private (A)
Citations
6 citations on file for this inspection.
1910.23 C01
- Issued
- Jun 24, 2014
- Abate by
- Aug 13, 2014
- Penalty
- Initial $4,900 · Current $3,430 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toe boards: On and about 5/28/14, employees working on the roof cleaning the evaporators were not protected from falling from the roof by guardrails or other forms of fall protection.
Recent events (2)
- · I (S) $3430
- · Z (S) $4900
1910.28 A01
- Issued
- Jun 24, 2014
- Abate by
- Jul 2, 2014
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.28(a)(1): Scaffolds were not furnished or erected in accordance with this standard for persons engaged in work that could not be done safely from the ground or from solid construction: On and about 5/28/14, employees operating valves near the ceiling of the boiler room used a 2x10 plank spanning between the two boilers as a scaffold to reach the valves.
Recent events (2)
- · I (S) $2450
- · Z (S) $3500
1910.303 B02
- Issued
- Jun 24, 2014
- Abate by
- Jul 2, 2014
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On and about 5/28/14, a 220v range plug receptacle designed for wall mounting was used as a flexible cord end.
Recent events (2)
- · I (S) $2450
- · Z (S) $3500
1910.303 B07 I
- Issued
- Jun 24, 2014
- Abate by
- Jul 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: On and about 5/28/14, electrical panel boxes and junction boxes had multiple unused openings from previously removed installations that were not closed to prevent inadvertent contact or accumulations of debris.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 B02 I
- Issued
- Jun 24, 2014
- Abate by
- Jul 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: On and about 5/28/14, 3 junction boxes did not have covers on them to protect the connections and to contain sparks in the event of arcing.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 G02 III
- Issued
- Jun 24, 2014
- Abate by
- Jul 2, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: On and about 5/28/14, a flexible SO cable feeding a receptacle for a portable welder was run through an opening in the bottom of a breaker panel without a strain relief or bushing to prevent the weight of the cable from pulling on the terminal screws in the panel.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections in this industry (NAICS 311514)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339787079.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.