Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: PACKERLAND WHEY PRODUCTS, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of PACKERLAND WHEY PRODUCTS, INC. in 407 4TH STREET, LUXEMBURG, WI 54217 (NAICS 311514). OSHA activity number 339787079.

Watch Packerland Whey Products, INC. — free Get an email when a new federal OSHA severe-injury report for Packerland Whey Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
407 4TH STREET
City
LUXEMBURG
State
WI
ZIP
54217
Mailing
407 4TH STREET, LUXEMBURG, WI 54217
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311514
Employees
30
Ownership type
A

6 citations on file for this inspection.

1910.23 C01

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $3430.00 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toe boards:     On and about 5/28/14, employees working on the roof cleaning the evaporators were not protected from falling from the roof by guardrails or other forms of fall protection.
Recent events (2)
  • — I (S) $3430
  • — Z (S) $4900

1910.28 A01

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $2450.00 Reduced
29 CFR 1910.28(a)(1):  Scaffolds were not furnished or erected in accordance with this standard for persons engaged in work that could not be done safely from the ground or from solid construction:    On and about 5/28/14, employees operating valves near the ceiling of the boiler room used a 2x10 plank spanning between the two boilers as a scaffold to reach the valves.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.303 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $3500.00 · Current $2450.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:     On and about 5/28/14, a 220v range plug receptacle designed for wall mounting was used as a flexible cord end.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.303 B07 I

Serious Gravity 5 4 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  On and about 5/28/14, electrical panel boxes and junction boxes had multiple unused openings from previously removed installations that were not closed to prevent inadvertent contact or accumulations of debris.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 3 instances 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:   On and about 5/28/14, 3 junction boxes did not have covers on them to protect the connections and to contain sparks in the event of arcing.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:   On and about 5/28/14, a flexible SO cable feeding a receptacle for a portable welder was run through an opening in the bottom of a breaker panel without a strain relief or bushing to prevent the weight of the cable from pulling on the terminal screws in the panel.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339787079.