WICHITA, KS —
OSHA Inspection: METAL FINISHING CO. INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of METAL FINISHING CO. INC. in 1423 S. MCLEAN BLVD, WICHITA, KS 67212 (NAICS 332813). OSHA activity number 339793929.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- METAL FINISHING CO. INC.
- Site address
- 1423 S. MCLEAN BLVD
- City
- WICHITA
- State
- KS
- ZIP
- 67212
- Mailing
- 1423 S. MCLEAN BLVD, WICHITA, KS 67212
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332813
- Employees
- 84
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.23 C01
- Issued
- Jul 8, 2014
- Penalty
- Initial $5,390 · Current $2,695 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: In the Hard Anodized Prep Overhead Storage area, the gate was in the open position, exposing employees to a fall hazard of approximately 10 feet to the concrete floor below.
Recent events (2)
- — I (O) $2695
- — Z (S) $5390
1910.23 E01
- Issued
- Jul 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $2,310 · Current $1,155 Reduced
General-duty citation text
29 CFR 1910.23(e)(1): Standard railing(s) did not consist of top rail, intermediate rail and/or posts and/or did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform runway, or ramp level: In the Hard Anodized Prep Overhead Storage area, the area was guarded with a railing that was approximately 32" high, exposing employees to a fall hazard of approximately 10 feet to the concrete floor below. The Lab Manager stated that he gets up in this area a couple of times a year. The maintenance lead reported that he gets in this area. The hard anodized area employees get up on the second level daily, because they stage parts in this area.
Recent events (2)
- — I (O) $1155
- — Z (S) $2310
1910.24 D
- Issued
- Jul 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $2,310 · Current $1,155 Reduced
General-duty citation text
29 CFR 1910.24(d): Stair width of fixed stairways was not at least 22 inches wide: Stairs used to access the Hard Anodized Overhead Storage Area, had an inadequate stair width in that the bottom step was only approximately 12 inches wide and approximately 27 inches deep, when ascending the stairs.
Recent events (2)
- — I (O) $1155
- — Z (S) $2310
1910.304 G05
- Issued
- Jul 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $2,310 · Current $1,155 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: In the Human Resources Storage Room, a 850 Watt Whirlpool microwave used for heating food was ungrounded, in that the grounding prong had been broken off the attachment plug, exposing employees to an electrical shock hazard.
Recent events (2)
- — I (S) $1155
- — Z (S) $2310
1910.305 G01 IV A
- Issued
- Jul 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: In the Human Resources Storage Room, a 850 Watt Whirlpool microwave used for heating food was permanently plugged into a two-wire extension cord, exposing employees to an electrical shock hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Jul 8, 2014
- Abate by
- Aug 1, 2014
- Penalty
- Initial $4,620 · Current $2,310 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: In the zinc plating area on the south wall, a 480 VAC Nickel Temperature Controller enclosure box had four separate openings, exposing employees to an electrical shock hazard. METAL FINISHING CO., INC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.305(b)(1)(ii)), which was contained in OSHA inspection number 315087338, citation number 01, item number 012 and was affirmed as a final order on (7-11-2011), with respect to a workplace located at 1423 S. McLean Blvd, Wichita, KS 67213.
Recent events (2)
- — I (R) $2310
- — Z (R) $4620
More inspections at Metal Finishing CO. INC.
View Metal Finishing CO. INC.'s full OSHA safety record →
More inspections in this industry (NAICS 332813)
More inspections in KS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339793929.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.