Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: METAL FINISHING CO. INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of METAL FINISHING CO. INC. in 1423 S. MCLEAN BLVD, WICHITA, KS 67212 (NAICS 332813). OSHA activity number 339793929.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Metal Finishing CO. INC. — free Get an email when a new federal OSHA severe-injury report for Metal Finishing CO. INC. is published. One employer, no account, unsubscribe in one click.
Site address
1423 S. MCLEAN BLVD
City
WICHITA
State
KS
ZIP
67212
Mailing
1423 S. MCLEAN BLVD, WICHITA, KS 67212
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
84
Ownership type
A

6 citations on file for this inspection.

1910.23 C01

Other-than-serious 1 instance 2 exposed
Issued
Jul 8, 2014
Penalty
Initial $5,390 · Current $2,695 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:    In the Hard Anodized Prep Overhead Storage area, the gate was in the open position, exposing employees to a fall hazard of approximately 10 feet to the concrete floor below.
Recent events (2)
  • — I (O) $2695
  • — Z (S) $5390

1910.23 E01

Other-than-serious 1 instance 2 exposed
Issued
Jul 8, 2014
Abate by
Aug 1, 2014
Penalty
Initial $2,310 · Current $1,155 Reduced
29 CFR 1910.23(e)(1): Standard railing(s) did not consist of top rail, intermediate rail and/or posts and/or did not have a vertical height of 42 inches (106.7 cm) nominal from upper surface of top rail to floor, platform runway, or ramp level:    In the Hard Anodized Prep Overhead Storage area, the area was guarded with a railing that was approximately 32" high, exposing employees to a fall hazard of approximately 10 feet to the concrete floor below.  The Lab Manager stated that he gets up in this area a couple of times a year.  The maintenance lead reported that he gets in this area.  The hard anodized area employees get up on the second level daily, because they stage parts in this area.
Recent events (2)
  • — I (O) $1155
  • — Z (S) $2310

1910.24 D

Other-than-serious 1 instance 6 exposed
Issued
Jul 8, 2014
Abate by
Aug 1, 2014
Penalty
Initial $2,310 · Current $1,155 Reduced
29 CFR 1910.24(d): Stair width of fixed stairways was not at least 22 inches wide:    Stairs used to access the Hard Anodized Overhead Storage Area, had an inadequate stair width in that the bottom step was only approximately 12 inches wide and approximately 27 inches deep, when ascending the stairs.
Recent events (2)
  • — I (O) $1155
  • — Z (S) $2310

1910.304 G05

Serious Gravity 1 1 instance 1 exposed
Issued
Jul 8, 2014
Abate by
Aug 1, 2014
Penalty
Initial $2,310 · Current $1,155 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  In the Human Resources Storage Room, a 850 Watt Whirlpool microwave used for heating food was ungrounded, in that the grounding prong had been broken off the attachment plug, exposing employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $1155
  • — Z (S) $2310

1910.305 G01 IV A

Serious Gravity 1 1 instance 1 exposed
Issued
Jul 8, 2014
Abate by
Aug 1, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  In the Human Resources Storage Room, a 850 Watt Whirlpool microwave used for heating food was permanently plugged into a two-wire extension cord, exposing employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Repeat Gravity 1 1 instance 1 exposed
Issued
Jul 8, 2014
Abate by
Aug 1, 2014
Penalty
Initial $4,620 · Current $2,310 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  In the zinc plating area on the south wall, a 480 VAC Nickel Temperature Controller enclosure box had four separate openings, exposing employees to an electrical shock hazard.   METAL FINISHING CO., INC was previously cited for a violation of this occupational safety and health standard or its equivalent standard (29 CFR 1910.305(b)(1)(ii)), which was contained in OSHA inspection number 315087338, citation number 01, item number 012 and was affirmed as a final order on (7-11-2011), with respect to a workplace located at 1423 S. McLean Blvd, Wichita, KS 67213.
Recent events (2)
  • — I (R) $2310
  • — Z (R) $4620

View Metal Finishing CO. INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339793929.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.