Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,201Inspections Most recent open 2026-08-31 Last loaded 2026-09-03

OSHA Inspection: ABCD HOLDINGS, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ABCD HOLDINGS, LLC in 198 EAST STREET, WARE, MA 01082 (NAICS 423930). OSHA activity number 339794174.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Abcd Holdings, LLC for free Get an email when a new federal OSHA severe-injury report for Abcd Holdings, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
ABCD HOLDINGS, LLC
Site address
198 EAST STREET
City
WARE
State
MA
ZIP
01082
Mailing
198 EAST STREET, WARE, MA 01082
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
6
Ownership type
Private (A)

9 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 4, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:      Workshop, Tri-County Recycling, 198 East Street, Ware, Massachusetts; On or about June 3, 2014 the exit door in the workshop was locked with a dead bolt preventing ready egress for employees in an emergency.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2000

1910.157 C01

Serious Gravity 5 3 instances 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 8, 2014
Penalty
Initial $1,600 · Current $1,000 Reduced
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:      Tri-County Recycling, Workshop, 198 East Street, Ware, Massachusetts; On or about June 3, 2014 fire extinguishers in the facility were blocked by equipment:    a.  Behind desk in back of shop  b.  Adjacent to the air compressor  c.  In the garage area in the back
Recent events (2)
  • · I (S) $1000
  • · Z (S) $1600

1910.157 C04

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(4): Portable fire extinguishers were not maintained in a fully charged and operable condition:  Workshop, Tri-County Recycling, 198 East Street, Ware, Massachusetts; Fire extinguishers in the facility were not maintained in proper working order with at least one extinguisher having no charge.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 15, 2014
Penalty
Initial $2,000 · Current $1,500 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:    Tri-County Recycling, 198 East Street, Ware, Massachusetts; On or about June 3, 2014 the employer used relocatable power taps and 2 to 6 electrical adapters outside of their listing and labeling to provide power to equipment in the facility.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2000

1910.303 G01

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 8, 2014
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:      Facility wide, Tri-County Recycling, 198 East Street, Ware, Massachusetts;  Electrical distribution panels were blocked by equipment preventing ready and safe operation of the overcurrent devices in the equipment.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2000

1910.305 A02 II

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 8, 2014
Penalty
Initial $2,000 · Current $0 Reduced
29 CFR 1910.305(a)(2)(ii): Temporary wiring was not removed immediately upon completion of the project or purpose for which the wiring was installed:    Tri-County Recycling, 198 East Street, Ware, Massachusetts;  On or about June 3, 2014 temporary wiring was left plugged into outlets after the completion of the purpose it was used.
Recent events (2)
  • · I (S) $0
  • · Z (S) $2000

1910.305 G01 IV A

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Facility wide, Tri-County Recycling, 198 East Street, Ware, Massachusetts; Extension cords and relocatable power taps were used in lieu of permanent wiring in the workshop to power a variety of equipment.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    By microwave and radio in workshop, Tri-County Recycling, 198 East Street, Ware, Massachusetts;  On or about June 3, 2014 a power cord plugged into a relocatable power tap had insufficient strain relief with the outer insulation pulled from the male plug end.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 6 exposed
Issued
Jul 29, 2014
Abate by
Aug 4, 2014
Penalty
Initial $2,000 · Current $1,800 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    Tri-County Recycling, 198 East Street, Ware, Massachusetts;  On or about June 3, 2014 electrical equipment had missing knockouts exposing employees to electrical shock hazards:    a.     the wall hung distribution panel in the workshop had multiple missing knockouts   b.     junction box in the workshop was missing knockouts
Recent events (2)
  • · I (S) $1800
  • · Z (S) $2000

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339794174.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.