MAYAGUEZ, PR —
OSHA Inspection: USDA-NRCS-ECOLOGICAL SCIENCE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of USDA-NRCS-ECOLOGICAL SCIENCE in 2200 PEDRO ALBIZU CAMPOS AVE, APT 23, MAYAGUEZ, PR 00680 (NAICS 924120). OSHA activity number 339796450.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- USDA-NRCS-ECOLOGICAL SCIENCE
- Site address
- 2200 PEDRO ALBIZU CAMPOS AVE, APT 23
- City
- MAYAGUEZ
- State
- PR
- ZIP
- 00680
- Mailing
- 2200 PEDRO ALBIZU CAMPOS AVE, APT 23, MAYAGUEZ, PR 00680
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 4
- Ownership type
- D
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 9, 2014
- Abate by
- Oct 3, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling: On or about 06/03/14, at 2200 Pedro Albizu Campos Ave., Apt 23, Mayaguez, PR, in the Soil Conservationist's work area, an uninterruptible power supply was not directly connected to a permanently installed branch circuit receptacle. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Sep 9, 2014
- Abate by
- Nov 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Services, feeders, and branch circuits. Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident: On or about 06/03/14, at 2200 Pedro Albizu Campos Ave., Apt. 23, Mayaguez, PR, the circuit breakers or fuses in the electrical panel were not identified or labeled to show the locations of the building whose circuits they protect. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Sep 9, 2014
- Abate by
- Nov 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed: On or about 06/03/14, at 2200 Pedro Albizu Campos Ave., Apt 23, Mayaguez, PR, in the back exterior wall, openings in the electrical panel board were not closed. PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.