SYRACUSE, NY —
OSHA Inspection: UPSTATE NIAGARA COOPERATIVE INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of UPSTATE NIAGARA COOPERATIVE INC. in 6361 THOMPSON ROAD, SYRACUSE, NY 13206 (NAICS 424430). OSHA activity number 339802811.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UPSTATE NIAGARA COOPERATIVE INC.
- Site address
- 6361 THOMPSON ROAD
- City
- SYRACUSE
- State
- NY
- ZIP
- 13206
- Mailing
- 6361 THOMPSON ROAD, SYRACUSE, NY 13206
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424430
- Employees
- 31
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.37 A04
- Issued
- Jun 26, 2014
- Abate by
- Jul 16, 2014
- Penalty
- Initial $2,550 · Current $2,550
General-duty citation text
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times: a) Warehouse at exit door, on or about 6/10/14: Emergency lighting was not functioning. b) Office, on or about 6/10/14: Emergency lighting was not functioning. Abatement certification must be submitted for these items.
Recent events (2)
- — I (O) $2550
- — Z (S) $2550
1910.157 E03
- Issued
- Jun 26, 2014
- Abate by
- Jul 16, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: a) Warehouse, on or about 6/10/14: Two Badger portable fire extinguishers were last inspected May, 2008. b) Freezer, on or about 6/10/14: A Badger portable fire extinguisher was last inspected May, 2008. c) Warehouse by battery chargers, on or about 6/10/14: A Badger portable fire extinguisher was last inspected May, 2008. d) Offices, on or about 6/10/14: An Amerex portable fire extinguisher was last inspection May, 2008. Abatement certification must be submitted for these items.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.304 G05
- Issued
- Jun 26, 2014
- Abate by
- Jul 16, 2014
- Penalty
- Initial $2,550 · Current $2,550
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Warehouse, on or about 6/10/14: A green extension cord providing current to a vending machine and a paper shredder was not grounded in that the ground pin was missing from the plug end. b) Warehouse, battery charging area, on or about 6/10/14: An orange extension cord used to charge the battery on a pallet jack was not grounded in that the ground pin was missing from the plug end. Abatement certification must be submitted for these items.
Recent events (2)
- — I (O) $2550
- — Z (S) $2550
1910.305 G01 IV A
- Issued
- Jun 26, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Loading Dock, Doors 1 and 2, on or about 6/10/14: Extension cord providing current to the pump for the DEF was strung overhead and being used as permanent wiring. b) Warehouse, on or about 6/10/14: Two extension cords providing current to a pump for the washer fluid were strung along the storage racking to an outlet and being used as permanent wiring. c) Warehouse, on or about 6/10/14: A green extension cord providing current to a vending machine and a paper shredder was strung along the floor and being used as permanent wiring. Abatement certification must be submitted for these items.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.178 L04 III
- Issued
- Jun 26, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years: a) At the establishment, on or about 6/10/14: An evaluation of each powered industrial truck operator's performance was not conducted at least once every three years in that the last evaluations conducted were February, 2010. Abatement certification must be submitted for this item.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Upstate Niagara Cooperative INC.
View Upstate Niagara Cooperative INC.'s full OSHA safety record →
More inspections in this industry (NAICS 424430)
More inspections in NY