COLUMBUS, OH —
OSHA Inspection: BIG LOTS, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BIG LOTS, INC. in 500 PHILLIPI ROAD, COLUMBUS, OH 43228 (NAICS 493110). OSHA activity number 339802985.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BIG LOTS, INC.
- Site address
- 500 PHILLIPI ROAD
- City
- COLUMBUS
- State
- OH
- ZIP
- 43228
- Mailing
- 300 PHILLIPI ROAD, COLUMBUS, OH 43228
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 493110
- Employees
- 440
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.110 F02 I
- Issued
- Jul 31, 2014
- Penalty
- Initial $4,400 · Current $4,400
General-duty citation text
29 CFR 1910.110(f)(2)(i): Containers in storage shall be located so as to minimize exposure to excessive temperature rise, physical damage, or tampering by unauthorized persons. a. The employer had approximately 33 flammable gas cylinders behind the facility in a rack system. The rack was not secured to prevent unauthorized tampering. Employees were exposed to a fire/explosion hazard.
Recent events (3)
- — F (S) $4400
- — C (S) $4400
- — Z (S) $4400
1910.132 E
- Issued
- Jul 31, 2014
- Penalty
- Initial $3,300 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.132(e): Defective and damaged equipment. Defective or damaged personal protective equipment shall not be used. a. Employees were using a stock picker Serial #1A219496 with a lanyard that was frayed. Lanyard Model 01122. The employees were exposed to a fall hazard of up to 20 feet.
Recent events (3)
- — F (S) $1000
- — C (S) $3300
- — Z (S) $3300
1910.132 F01 III
- Issued
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(f)(1)(iii): How to properly don, doff, adjust, and wear PPE; a. Employees wear assigned to wear fall protection for the utilization of the cherry picker. Employees were not properly trained on how to don, doff, and adjust the fall protection. Employees were exposed to fall related injuries.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jul 31, 2014
- Penalty
- Initial $5,500 · Current $1,879 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. a. At receiving bay 251 the Versa light model 420 had damaged strain relief where the flexible cord came out of the light fixture. The employees were exposed to a contact with 110-120 Volt electrical current hazard. b. At bay door 410 the flexible cord from the Versa Light model 420 had damaged strain relief where the flexible cord came out of the light fixture. The employees were exposed to a contact with 110-120 Volt electrical current hazard.
Recent events (3)
- — F (S) $1879
- — C (S) $5500
- — Z (S) $5500
1910.334 A02 II
- Issued
- Jul 31, 2014
- Penalty
- Initial $7,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made. a. On June 11, 2014, near the battery changing terminal, the industrial box fan cord insulation had been damaged and taped with electrical tape. Under the electrical tape their were bare copper conductors, thereby exposing employees to a contact with electrical current hazard.
Recent events (3)
- — F (S) $3500
- — C (S) $7000
- — Z (S) $7000
1910.212 A05
- Issued
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(5): Exposure of blades. When the periphery of the blades of a fan is less than seven (7) feet above the floor or working level, the blades shall be guarded. The guard shall have openings no larger than one-half (1/2) inch. a. On June 11, 2014, the industrial box fan located next to the battery changing station had broken sections of guard leaving 1 inch opening in the guarding. Employees were exposed to an amputation hazard.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.176 B
- Issued
- Jul 31, 2014
- Penalty
- Initial $27,500 · Current $7,000 Reduced
General-duty citation text
29 CFR 1910.176(b): Secure storage. Storage of material shall not create a hazard. Bags, containers, bundles, etc., stored in tiers shall be stacked, blocked, interlocked and limited in height so that they are stable and secure against sliding or collapse. a. The rack 401-001-3-1 was bent at the base, resulting in employees being exposed to caught in and struck by hazards. b. The rack 402-072-1-1 was bend on the weld, the rack had a 2,500 pound capacity per pallet spot, each pallet in the area was 2,200 pounds. The employees were exposed to caught in and struck by hazards. c. The rack 406-136-1-1 was cracked at the welding seem, the rack had a rated capacity of 2,500 pounds per pallet spot, each pallet weighed 2,250 pounds. The employees were exposed to caught in and struck by hazards. Big Lots Inc. was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 314157280, citation number 1, item number 4 and was affirmed as a final order on September 30, 2010, with respect to a workplace located at 1010 Oneill Highway, Dunmore, PA 18512.
Recent events (3)
- — F (S) $7000
- — C (R) $27500
- — Z (R) $27500
1910.305 B01 II
- Issued
- Jul 31, 2014
- Penalty
- Initial $220 · Current $220
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a. The 120-208 Volt cabinet EP350UA78, near the 300 general office access had an unused opening, thereby exposing employees to a contact with electrical current. b. The knife switch box DSC400B33-1 had an unused opening at the base of the box, thereby exposing employees to contact with electrical current. Big Lots was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 108439, citation number 1, item number 2 and was affirmed as a final order on December 06, 2011, with respect to a workplace located at 300 Phillipi Road, Columbus, OH 43228.
Recent events (3)
- — F (R) $220
- — C (R) $220
- — Z (R) $220
More inspections at BIG Lots, INC.
View BIG Lots, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 493110)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339802985.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.