CHICAGO, IL —
OSHA Inspection: STANDARD FORWARDING LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of STANDARD FORWARDING LLC in 5260 W. 47TH ST., CHICAGO, IL 60638 (NAICS 484121). OSHA activity number 339804569.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STANDARD FORWARDING LLC
- Site address
- 5260 W. 47TH ST.
- City
- CHICAGO
- State
- IL
- ZIP
- 60638
- Mailing
- 5260 W. 47TH ST., CHICAGO, IL 60638
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 484121
- Employees
- 89
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.157 C01
- Issued
- Dec 10, 2014
- Abate by
- Jan 29, 2015
- Penalty
- Initial $2,800 · Current $0 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury. a- Warehouse and Throughout Facility- On or about June 12, 2014, employer did not ensure that portable fire extinguishers were mounted and made readily accessible to employees. Thereby exposing employees to fire hazard(s).
Recent events (2)
- — I (O) $0
- — Z (S) $2800
1910.157 C04
- Issued
- Dec 10, 2014
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): The employer shall assure that portable fire extinguishers are maintained in a fully charged and operable condition and kept in their designated places at all times except during use. a. Warehouse and throughout facility- On or about 12 June 2014, employer did not ensure that portable fire extinguishers were maintained in a fully charged and operational condition. Thereby exposing employees to fire hazard(s).
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Dec 10, 2014
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. a. Ground floor, warehouse area- On or about 12 June 2014, employer did not ensure that corrosion and water damaged control panels were taken out-of-service. Thereby exposing employees to shock and electrocution hazard(s). 1. Electrical control panels controlling outside light fixture one through six against loading dock wall. 2. Electrical wall outlet near customer pick-up point. 3. Electrical surge protector (power tap) with burn damage energizing appliances.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.303 G01
- Issued
- Dec 10, 2014
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Space about electric equipment. Sufficient access and working space shall be provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment. a. Warehouse Area- on or about June 12, 2014, employees were required to access obstructed panel boxes. The panel boxes were obstructed with several wooden pallets of bagged mineral product, one wooden pallet of 55 gallon containerized chemical product, and two stored pallet jacks. Thereby exposing employees to shock, electrocution, and fire hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01
- Issued
- Dec 10, 2014
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Conductors entering boxes, cabinets, or fittings. a. Ground floor, break room- On or about June 12, 2014, employer did not ensure that employees were protected against contact with energized wall switch. Top knockout was missing. Thereby exposing employees to shock and electrocution hazard.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 B02 I
- Issued
- Dec 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a. Ground floor, Warehouse and dock area- On or about June 12, 2014, employer did not ensure that employees were protected from exposed live conductors outside open junction boxes. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Dec 10, 2014
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Where run through doorways, windows, or similar openings; a. Ground floor break room- On or about June 12, 2014, employer did not ensure that orange ten (10) foot extension cords were not run through windows in the facility. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 I
- Issued
- Dec 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals. a. Warehouse loading docks- On or about June 12, 2014, Employer did not ensure live wires attached to external dock lights were not exposed. Thereby exposing employees to shock and electrocution hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Standard Forwarding LLC
View Standard Forwarding LLC's full OSHA safety record →
More inspections in this industry (NAICS 484121)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339804569.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.