Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,871Inspections Most recent open 2026-07-30 Last loaded 2026-08-02

OSHA Inspection: ADVANTAGE MANUFACTURING, A DIVISION OF CALDWELL MANUFACTURING CO., NA, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ADVANTAGE MANUFACTURING, A DIVISION OF CALDWELL MANUFACTURING CO., NA, LLC in 788 OLD DUTCH ROAD, VICTOR, NY 14564 (NAICS 332510). OSHA activity number 339808107.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Advantage Manufacturing, a Division of Caldwell Manufacturing CO., NA, LLC for free Get an email when a new federal OSHA severe-injury report for Advantage Manufacturing, a Division of Caldwell Manufacturing CO., NA, LLC is published. One employer, no account, unsubscribe in one click.
Site address
788 OLD DUTCH ROAD
City
VICTOR
State
NY
ZIP
14564
Mailing
788 OLD DUTCH ROAD, VICTOR, NY 14564
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332510
Employees
62
Ownership type
A

5 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 4 instances 4 exposed
Issued
Jul 9, 2014
Abate by
Aug 13, 2014
Penalty
Initial $3,400 · Current $2,040 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a)  Tool Room, on or about 6/12/14:  (2) Bridgeport milling machines were not provided with chuck guards to prevent contact with the serrated chuck or cutting bit.  b)  Tool Room, on or about 6/12/14:  Powermatic drill press was not was not provided with adequate guarding to prevent contact with the serrated chuck or cutting bit.  c)  Press Department, on or about 6/12/14:  Ridgid drill press was not provided with guarding to prevent contact with the serrated chuck or cutting bit.  d)  CNC Department, on or about 6/12/14:  Grizzley drill press was not provided with adequate guarding to prevent contact with the serrated chuck and cutting bit.
Recent events (2)
  • · I (S) $2040
  • · Z (S) $3400

1910.303 B02

Serious Gravity 1 4 instances 4 exposed
Issued
Jul 9, 2014
Abate by
Aug 13, 2014
Penalty
Initial $2,550 · Current $1,530 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   a)  Press Department, near Minster 100 Ton Press, on or about 6/12/14:  A pendant cord with a metal receptacle box attached was used to provide power to equipment.  The metal box is listed for permanent mounting only.   b)  Press Department, near Minster #5 Press, on or about 6/12/14: A pendant cord with a metal receptacle box attached was used to  provide power to equipment.  The metal box is listed for permanent mounting only.    c)  Press Department, near Minster #43 Press, on or about 6/12/14:  A pendant cord with a metal receptacle box attached was used to provide power to equipment.  The metal box is listed for permanent mounting only.  d)  CNC Department, near Haas #4, on or about 6/12/14:  A pendant cord with a metal receptacle box attached was used to provide power to equipment.  The metal box is listed for permanent mounting only.
Recent events (2)
  • · I (S) $1530
  • · Z (S) $2550

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 9, 2014
Abate by
Jul 29, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a)  Press Department, near the Bliss 80-Ton Press, on or about 6/12/14:  An extension cord was used as a substitute for fixed wiring to provide power to a conveyor and task light.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G02 III

Serious Gravity 1 3 instances 5 exposed
Issued
Jul 9, 2014
Abate by
Aug 13, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:   a)  Press Department, on or about 6/12/14:  Drop cord near #43 Minster press was not provided with strain relief.  b)  CNC Department, on or about 6/12/14:  Drop cord near #4 Haas CNC was not provided with strain relief.  c)  CNC Department, on or about 6/12/14:  Diehl drill press power cord was not provided with strain relief.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.304 G05

Serious Gravity 5 2 instances 3 exposed
Issued
Jul 9, 2014
Penalty
Initial $3,400 · Current $2,040 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective:  a)  Shipping and Receiving, on or about 6/12/14:  Industrial floor fan was not provided with a continuous path to ground.  b)  Press Department, on or about 6/12/14:  Marley industrial fan was not provided with a continuous path to ground in that the ground pin missing.
Recent events (2)
  • · I (S) $2040
  • · Z (S) $3400

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339808107.