OSHA Inspection: KENT FABRICATIONS, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of KENT FABRICATIONS, INC. in 171 MATTAKEESETT STREET, UNIT #8, PEMBROKE, MA 02359 (NAICS 332323). OSHA activity number 339808578.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Kent Fabrications, INC. — free Get an email when a new federal OSHA severe-injury report for Kent Fabrications, INC. is published. One employer, no account, unsubscribe in one click.
Site address
171 MATTAKEESETT STREET, UNIT #8
City
PEMBROKE
State
MA
ZIP
02359
Mailing
171 MATTAKEESETT STREET, UNIT #8, PEMBROKE, MA 02359
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332323
Employees
8
Ownership type
A

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 5 exposed
Issued
Dec 3, 2014
Abate by
Apr 21, 2015
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing and labeling:  Establishment:  The following electrical equipment were not used in accordance with their listing and labeling: a)  Bay #7 - A temporary power tap (TPT) was used to energize portable equipment such as a 14-inch wood band saw, hand grinder, rotor jigsaw and a battery charger.  The TPT was connected to an extension cord plugged into a double duplex receptacle. b) Bay #8 - Double duplex receptacle boxes designed to be mounted were used as pendant boxes.   These boxes energized equipment such as the Marvel band saw, Miller Millermatic 250 welding machine, and Pedrazzoli 2000 chop saw.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1910.304 F01 IV

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 3, 2014
Abate by
Apr 21, 2015
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  Bay #8:  Circuit panels that energized equipment such as the lights, drill press, and various portable equipment such as band saws and welding machines were blocked by items in storage such as metal stock and unused equipment.
Recent events (2)
  • — I (S) $1120
  • — Z (S) $1600

1910.305 G01 IV

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 3, 2014
Abate by
Apr 21, 2015
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):  Bay #7 & #8:  Flexible cords that were used to energize various equipment such as peripheral equipment for the Supermax Drill Press located in Bay #8 ran through a wall and was connected to a receptacle in Bay #7.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2000

1910.37 B05

Other-than-serious 1 instance 8 exposed
Issued
Dec 3, 2014
Abate by
Apr 21, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):   Bay #7:  The back door was marked with an illuminated sign as an exit but there was no safe access to the door and was blocked by items in storage such as metal bars.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Kent Fabrications, INC.'s full OSHA safety record →