KAILUA, HI —
OSHA Inspection: MACY'S WEST STORES, INC. -KAILUA 477
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MACY'S WEST STORES, INC. -KAILUA 477 in 573 KAILUA RD., KAILUA, HI 96734 (NAICS 452111). OSHA activity number 339818429.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MACY'S WEST STORES, INC. -KAILUA 477
- Site address
- 573 KAILUA RD.
- City
- KAILUA
- State
- HI
- ZIP
- 96734
- Mailing
- 573 KAILUA RD., KAILUA, HI 96734
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452111
- Employees
- 16
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.157 C01
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $2,100 · Current $0 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: a) On or about June 20, 2014, in the shipping and receiving area, 3 portable fire extinguishers mounted on the wall did not have signage indicating their locations.
Recent events (2)
- — I (O) $0
- — Z (S) $2100
1910.303 B02
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $2,800 · Current $2,800
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about June 20, 2014, in the break room, high power load appliances, such as a Black & Decker toaster oven, Keurig coffee maker, and a Shape microwave oven, were plugged into a Relocatable Power Tap (RPT).
Recent events (2)
- — I (O) $2800
- — Z (S) $2800
1910.304 B04 II B
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle excessed a total cord- and plug-connected load of the maximum specified in Table S-4: a) On or about June 20, 2014, in the break room, high power load appliances, such as a Black & Decker toaster oven, Keurig coffee maker, and a Shape microwave oven, while plugged into a Relocatable Power Tap (RPT) and operated simultaneously exceed the circuit's current capacity.
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.305 B02
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $2,100 · Current $1,575 Reduced
General-duty citation text
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) On or about June 20, 2014, employees working in the Estee Lauder Kiosk, were exposed to an electrical hazard due to a missing faceplate on a receptacle.
Recent events (2)
- — I (O) $1575
- — Z (S) $2100
1910.1200 G01
- Issued
- Jul 3, 2014
- Abate by
- Jul 24, 2014
- Penalty
- Initial $4,200 · Current $0 Reduced
General-duty citation text
29 CFR 1910.1200(g)(1): The employer did not have a material safety data sheet for each hazardous chemical which they used: a) On or about June 20, 2014, in the shipping/receiving area, employees were exposed to chemical hazards while using hazardous chemicals and not having the Material Safety Data Sheets available.
Recent events (2)
- — I (O) $0
- — Z (S) $4200
1910.157 E02
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) On or about June 20, 2014, in the shipping/receiving area, 3 portable fire extinguishers did not have documented monthly inspections.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.159 C10
- Issued
- Jul 3, 2014
- Abate by
- Jul 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: a) On or about June 20, 2014, in the Visual room, employees were exposed to a fire hazard due to material stored within 18 inches of the automatic fire sprinkler heads.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.304 G01 II
- Issued
- Jul 3, 2014
- Abate by
- Jul 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space about electric equipment rated 600 volts, nominal, or less was used for storage: a) On or about June 20, 2014, in the shipping/receiving area, the work space in front of the 120-240 Vac Circuit Breaker Distribution Panel was not kept clear for a minimum of 3 feet.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections in this industry (NAICS 452111)
More inspections in HI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339818429.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.