OSHA Inspection: DELTA ELECTRIC COMPANY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of DELTA ELECTRIC COMPANY in 1650 COUNTY ROAD 210 WEST, JACKSONVILLE, FL 32259 (NAICS 238210). OSHA activity number 339822843.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Delta Electric Company — free Get an email when a new federal OSHA severe-injury report for Delta Electric Company is published. One employer, no account, unsubscribe in one click.
Site address
1650 COUNTY ROAD 210 WEST
City
JACKSONVILLE
State
FL
ZIP
32259
Mailing
1840 SCRUBBY BLUFF ROAD, KINGSLAND, GA 31548
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

3 citations on file for this inspection.

1910.332 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 18, 2014
Abate by
Jan 7, 2015
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:       a. On or about June 25, 2014, an employee was not trained in and familiar with the safety-related work practices for lockout and tagging of electrical circuits as required by 1910.333(b)(2) and the employee was not trained in and familiar with the safety-related work practices for using insulated tools when working near exposed energized conductors as required by 1910.335(a)(2)(I), which directly resulted in the employee sustaining an electrocution-type fatality.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $2800

1910.333 C02

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 18, 2014
Penalty
Initial $4,900 · Current $3,900 Reduced
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools:    a. On or about June 25, 2014, an unqualified employee was working on or near an energized florescent lamp ballast and exposed to electrical shock hazards, which directly resulted in the employee sustaining an electrocution-type fatality.
Recent events (2)
  • — I (S) $3900
  • — Z (S) $4900

1910.335 A02 II

Serious Gravity 10 1 instance 1 exposed
Issued
Nov 18, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.335(a)(2)(ii): When normally enclosed live parts were exposed for maintenance or repair, they were not guarded to protect unqualified persons from contact with the live parts:  a. On or about June 25, 2014, an unqualified employee was repairing an energized florescent lamp ballast and not guarded to protect this employee from contact with live parts which resulted in the employee sustaining an electrocution-type fatality.
Recent events (2)
  • — I (S) $2800
  • — Z (S) $2800

View Delta Electric Company's full OSHA safety record →