KELLER, WA —
OSHA Inspection: BUREAU OF INDIAN AFFAIRS COLVILLE AGENCY, BRANCH OF ROADS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of BUREAU OF INDIAN AFFAIRS COLVILLE AGENCY, BRANCH OF ROADS in HWY 21, BLDG. 87, KELLER, WA 99140 (NAICS 921190). OSHA activity number 339824807.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- HWY 21, BLDG. 87
- City
- KELLER
- State
- WA
- ZIP
- 99140
- Mailing
- PO BOX 111, NESPELEM, WA 99155
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 921190
- Employees
- 2
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.38 A
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.38(a): The employer did not establish an emergency action plan whenever an OSHA standard in this part required one and did not meet the requirements of paragraphs (a)-(f)(3) of this section: a) Branch of Roads Shop, where employees would evacuate the building in the event of a fire, the fire extinguishers located throughout the work place were not inspected on an annual or monthly basis. 29 CFR 1910.157(a): Scope and application. The requirements of this section apply to the placement, use, maintenance, and testing of portable fire extinguishers provided for the use of employees. Paragraph (d) of this section does not apply to extinguishers provided for employee use on the outside of workplace buildings or structures. Where extinguishers are provided but are not intended for employee use and the employer has an emergency action plan and a fire prevention plan that meet the requirements of 29 CFR 1910.38 and 29 CFR 1910.39 respectively, then only the requirements of paragraphs (e) and (f) of this section apply.
Recent events (1)
- — Z (S) $0
1910.39 B
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.39(b):The employer did not establish a fire prevention plan that was in writing, kept in the workplace, and made available to employees for review (an employer with 10 or fewer employees may communicate the plan orally to employees): a) Branch of Roads Shop, where employees would evacuate the building in the event of a fire, the fire extinguishers located throughout the work place were not inspected on an annual or monthly basis. 29 CFR 1910.157(a): Scope and application. The requirements of this section apply to the placement, use, maintenance, and testing of portable fire extinguishers provided for the use of employees. Paragraph (d) of this section does not apply to extinguishers provided for employee use on the outside of workplace buildings or structures. Where extinguishers are provided but are not intended for employee use and the employer has an emergency action plan and a fire prevention plan that meet the requirements of 29 CFR 1910.38 and 29 CFR 1910.39 respectively, then only the requirements of paragraphs (e) and (f) of this section apply.
Recent events (1)
- — Z (S) $0
1910.157 E01
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(1): The employer was not responsible for the inspection, maintenance and testing of all portable fire extinguishers in the workplace: a) Branch of Roads, where fire extinguishers not inspected annually included: 1. Shop, where the Amerex fire extinguisher was equipped with an inspection tag dated October 2010. 2. Shop, where the ABC Nitrogen fire extinguisher was equipped with an inspection tag dated October 2010.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly: a) Branch of Roads, where fire extinguishers not inspected monthly included: 1. Shop, where the Amerex fire extinguisher was equipped with an inspection tag dated October 2010. 2. Shop, where the ABC Nitrogen fire extinguisher was equipped with an inspection tag dated October 2010.
Recent events (1)
- — Z (S) $0
1910.212 B
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machines designed for a fixed location were not anchored to prevent walking or moving: a) Shop, where the Delta 17 drill press was not anchored in place.
Recent events (1)
- — Z (S) $0
1910.215 B09
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) Shop, where the tongue guard on the Baldor pedestal grinder measured 1/2 inch from the abrasive wheel.
Recent events (1)
- — Z (S) $0
1910.303 G01 II
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Shop, where items including traffic cones and lumber were stored in front of the electrical panel located on the southeast wall.
Recent events (1)
- — Z (S) $0
1910.305 J01 I
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles may have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 2.44 m (8.0 ft) above the floor may have exposed terminals: a) Shop Restroom, where two unguarded single bulbs measured 7 feet 6 inches above floor level.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Aug 5, 2014
- Abate by
- Sep 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) Shop, where the receptacle located on the east wall was not equipped with a faceplate.
Recent events (1)
- — Z (O) $0
More inspections at Bureau of Indian Affairs Colville Agency, Branch of Roads
View Bureau of Indian Affairs Colville Agency, Branch of Roads's full OSHA safety record →
More inspections in this industry (NAICS 921190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339824807.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.