PALATINE, IL —
OSHA Inspection: THE INTEC GROUP, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE INTEC GROUP, INC. in 666 SOUTH VERMONT STREET, PALATINE, IL 60067 (NAICS 326199). OSHA activity number 339826919.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE INTEC GROUP, INC.
- Site address
- 666 SOUTH VERMONT STREET
- City
- PALATINE
- State
- IL
- ZIP
- 60067
- Mailing
- 666 SOUTH VERMONT STREET, PALATINE, IL 60067
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326199
- Employees
- 150
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.178 L02 II
- Issued
- Jul 21, 2014
- Abate by
- Aug 14, 2014
- Penalty
- Initial $3,060 · Current $2,142 Reduced
General-duty citation text
29 CFR 1910.178(l)(2)(ii): Training did not consist of a combination of formal instruction (e.g., lecture, discussion, interactive computer learning, video tape, written material), practical training (demonstrations performed by the trainer and practical exercises performed by the trainee), and evaluation of the operator's performance in the workplace: a) The employer had employees perform partial exercise and employer did not evaluate performance in the work place.
Recent events (2)
- — I (S) $2142
- — Z (S) $3060
1910.178 L06
- Issued
- Jul 21, 2014
- Abate by
- Aug 14, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.178(l)(6): The employer did not certify that each operator had been trained and evaluated as required by this paragraph (l). The certification shall include the name of the operator, the date of the training, the date of the evaluation, and the identity of the person(s) performing the training or evaluation: a) The employer failed to certify that each operator had been trained and evaluated by maintaining records that included the name of the operator, the date of the training, the date of the evaluation, and the identity of the person(s) performing the training or evaluation for the forklifts.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Jul 21, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $3,060 · Current $2,142 Reduced
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) Injection Molding Department - There were eight portable hand lamps with metal shells placed above the machines that did not have a ground pin.
Recent events (2)
- — I (S) $2142
- — Z (S) $3060
1910.305 J01 II
- Issued
- Jul 21, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(ii): Portable hand-lamps supplied through flexible cords were not equipped with a handle of molded composition or other material approved for the purpose, and a substantial guard attached to the lamp-holder or the handle: a) Injection Molding Department - Attached to the top of the machines to provide better lighting there was 18 portable hand lamps with a metal shell, non-insulated handles, and without a guard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.157 C01
- Issued
- Jul 21, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(1): The employer had portable fire extinguishers that were not mounted, located, identified and readily accessible to employees without subjecting the employees to possible injury: a) Technical Manager's Office - The ABC fire extinguisher was blocked by a file rack that was placed directly in front of the fire extinguisher and not readily accessible.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Jul 21, 2014
- Abate by
- Jul 31, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space about electrical equipment rated 600 volts, nominal, or was used for storage: a) Technical Manager Office - A tool box and books were placed directly in front of an electrical cabinet and other disconnect switches. b) Cooling Tower Area - A plastic drum and conveyor equipment was placed directly in front of an electrical cabinet and other disconnect switches.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at The Intec Group, INC.
View The Intec Group, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 326199)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339826919.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.