Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: 4 L EQUIPMENT LEASING LLC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of 4 L EQUIPMENT LEASING LLC. in 505 MAIN ST, WESTBURY, NY 11590 (NAICS 811118). OSHA activity number 339834236.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch 4 L Equipment Leasing LLC. for free Get an email when a new federal OSHA severe-injury report for 4 L Equipment Leasing LLC. is published. One employer, no account, unsubscribe in one click.
Site address
505 MAIN ST
City
WESTBURY
State
NY
ZIP
11590
Mailing
505 MAIN ST, WESTBURY, NY 11590
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811118
Employees
60
Ownership type
A

2 citations on file for this inspection.

1910.303 F02

Serious Gravity 1 1 instance 3 exposed
Issued
Sep 30, 2014
Abate by
Oct 10, 2014
Penalty
Initial $2,100 · Current $1,575 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Worksite, North side of shop - The circuit breaker used to control equipment, vents and lights in this area had switches not labeled as to what they controlled; on or about 7/2/14.  Note:  The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19.
Recent events (2)
  • · I (S) $1575
  • · Z (S) $2100

1910.305 B02 I

Serious Gravity 5 1 instance 3 exposed
Issued
Sep 30, 2014
Abate by
Oct 10, 2014
Penalty
Initial $3,500 · Current $2,625 Reduced
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:  a)  Worksite, North side of shop- an electrical circuit breaker box did not have a cover; on or about 7/2/14.   Note:  The employer is required to submit abatement certification for this item in accordance with 29 CFR 1903.19.
Recent events (2)
  • · I (S) $2625
  • · Z (S) $3500

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339834236.