Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: CLK HOSPITALITY, LLC

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of CLK HOSPITALITY, LLC in 1900 RIO GRANDE, AUSTIN, TX 78705 (NAICS 721110). OSHA activity number 339837221.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch CLK Hospitality, LLC for free Get an email when a new federal OSHA severe-injury report for CLK Hospitality, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1900 RIO GRANDE
City
AUSTIN
State
TX
ZIP
78705
Mailing
1900 RIO GRANDE, AUSTIN, TX 78705
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
92
Ownership type
A

6 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  On the roof, where maintenance employees were repairing Lennox rooftop A/C units, breakers controlling power to the units were located in a Square D panelboard box and were not labeled as to what they controlled, exposing employees to the hazards of electrical shock.
Recent events (2)
  • · I (S) $2100
  • · Z (S) $3500

1910.304 F01 IV

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  On the roof, where maintenance employees were repairing Lennox rooftop A/C units, breakers controlling the units were in a locked Square D panelboard cutout box, so employees were pulling fuses out of Enclosed Pullout Switch Boxes before servicing units, exposing employees to the hazards of electrical shock.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 D02

Serious Gravity 5 1 instance 4 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:  On the roof, Square D panelboard cutout box MH746WP for breakers controlling Lennox rooftop units was not dead front, exposing employees to the hazards of electrical shock.
Recent events (2)
  • · I (S) $2100
  • · Z (S) $3500

1910.305 G01 IV A

Serious Gravity 1 1 instance 10 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  In the Housekeeping Area, a Hampton Bay High Velocity Air Circulator with a job-made cord was series-connected to an extension cord that was plugged into a relocatable power tap in lieu of providing a fixed outlet, exposing employees to the hazards of fire.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 1 instance 10 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:  In the Housekeeping Area, a Hampton Bay High Velocity Air Circulator with a job-made cord was series-connected to an extension cord that was run through the false ceiling and dropped to a relocatable power tap across the room, exposing employees to the hazards of fire and electrical shock.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.1200 H01

Serious Gravity 1 1 instance 10 exposed
Issued
Sep 30, 2014
Abate by
Oct 8, 2014
Penalty
Initial $2,100 · Current $1,260 Reduced

Hazardous substances 22809010P104S103

29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:  For work performed at 1900 Rio Grande Street in Austin, Texas: On or about July 3, 2014 and at times prior thereto and thereafter, chemical hazard communication training provided to employees did not include information on the health hazards of chemicals associated with construction operations, and how to protect themselves from chemical exposures, including, but not limited to crystalline silica dust, Portland Cement, and styrene, exposing employees to the hazards of chemical inhalation.
Recent events (2)
  • · I (S) $1260
  • · Z (S) $2100

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339837221.