AUSTIN, TX ·
OSHA Inspection: CLK HOSPITALITY, LLC
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of CLK HOSPITALITY, LLC in 1900 RIO GRANDE, AUSTIN, TX 78705 (NAICS 721110). OSHA activity number 339837221.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CLK HOSPITALITY, LLC
- Site address
- 1900 RIO GRANDE
- City
- AUSTIN
- State
- TX
- ZIP
- 78705
- Mailing
- 1900 RIO GRANDE, AUSTIN, TX 78705
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 92
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.303 F02
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On the roof, where maintenance employees were repairing Lennox rooftop A/C units, breakers controlling power to the units were located in a Square D panelboard box and were not labeled as to what they controlled, exposing employees to the hazards of electrical shock.
Recent events (2)
- · I (S) $2100
- · Z (S) $3500
1910.304 F01 IV
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: On the roof, where maintenance employees were repairing Lennox rooftop A/C units, breakers controlling the units were in a locked Square D panelboard cutout box, so employees were pulling fuses out of Enclosed Pullout Switch Boxes before servicing units, exposing employees to the hazards of electrical shock.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 D02
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $3,500 · Current $2,100 Reduced
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front: On the roof, Square D panelboard cutout box MH746WP for breakers controlling Lennox rooftop units was not dead front, exposing employees to the hazards of electrical shock.
Recent events (2)
- · I (S) $2100
- · Z (S) $3500
1910.305 G01 IV A
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: In the Housekeeping Area, a Hampton Bay High Velocity Air Circulator with a job-made cord was series-connected to an extension cord that was plugged into a relocatable power tap in lieu of providing a fixed outlet, exposing employees to the hazards of fire.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 G01 IV D
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: In the Housekeeping Area, a Hampton Bay High Velocity Air Circulator with a job-made cord was series-connected to an extension cord that was run through the false ceiling and dropped to a relocatable power tap across the room, exposing employees to the hazards of fire and electrical shock.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.1200 H01
- Issued
- Sep 30, 2014
- Abate by
- Oct 8, 2014
- Penalty
- Initial $2,100 · Current $1,260 Reduced
22809010P104S103
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: For work performed at 1900 Rio Grande Street in Austin, Texas: On or about July 3, 2014 and at times prior thereto and thereafter, chemical hazard communication training provided to employees did not include information on the health hazards of chemicals associated with construction operations, and how to protect themselves from chemical exposures, including, but not limited to crystalline silica dust, Portland Cement, and styrene, exposing employees to the hazards of chemical inhalation.
Recent events (2)
- · I (S) $1260
- · Z (S) $2100