OSHA Inspection: ADELITA TAMALES & TORTILLA FACTORY

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ADELITA TAMALES & TORTILLA FACTORY in 1130 FRESNO DRIVE, SAN ANTONIO, TX 78201 (NAICS 311830). OSHA activity number 339843310.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Adelita Tamales & Tortilla Factory for free Get an email when a new federal OSHA severe-injury report for Adelita Tamales & Tortilla Factory is published. One employer, no account, unsubscribe in one click.
Site address
1130 FRESNO DRIVE
City
SAN ANTONIO
State
TX
ZIP
78201
Mailing
1130 FRESNO DRIVE, SAN ANTONIO, TX 78201
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311830
Employees
11
Ownership type
Private (A)

7 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 9, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:(a)             Tortilla production area:  On or about July 9, 2014, employee(s) were exposed to electrical hazards while operating the Casa Herrara Corn mixer machine, SN 96011290, and the power box on the wall nearest to it had a open knockout.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.305 G01 IV A

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 9, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:       Tortilla production area:  On or about July 9, 2014, employees were exposed to electrical hazards when a Superior Fryer machine, SN 50688, model no CT 133, was plugged into a extension cord that was used as temporary wiring.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.305 G01 IV B

Serious Gravity 5 3 instances 5 exposed
Issued
Oct 9, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:       a)  Tortilla production area:  On or about July 9, 2014, employee(s) were exposed to electrical and fire hazards when electrical cable powering a Superior tortilla machine SN 705608, model 3186-IUF, 230V, 2.8A was run through a hole in the ceiling.       b)  Tortilla production area:  On or about July 9, 2014, employee(s) were exposed to electrical and fire hazards when electrical cable powering a Lawrence Equipment tortilla machine SN 00299, model 18-10-9, 230V, 8A was run through a hole in the ceiling.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.305 G02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 9, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:       Tortilla production area:  On or about July 09, 2014, employees were exposed to electrical shock hazards when they were operating the Casa Herrara Corn mixer machine, SN 96011290, 7.6A, and the main power cord was spliced or cut and was repaired with electrical tape that was coming apart.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.333 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 9, 2014
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:       Tortilla production area:  On or about July 9, 2014, employee(s) were exposed to electrical shock hazards when a machine was moved and the electrical wiring was still activated and the employees were using a shop air line located directly next to the wiring which was left hanging out of the conduit and was covered in electrical tape.
Recent events (2)
  • · I (S) $1200
  • · Z (S) $2000

1910.157 C01

Other-than-serious 1 instance 10 exposed
Issued
Oct 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:       Rear Door:  On or about July 9, 2014, employees were exposed to fire hazards in the event of an emergency from accidental fires and the fire extinguishers did not have signage for identification.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.157 E03

Other-than-serious 1 instance 10 exposed
Issued
Oct 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:       On or about July 9, 2014, employees were exposed to fire hazards in the event of an emergency from accidental fires from cooking and baking and the fire extinguishers were not being maintained annually.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0