Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DEEM CABINETS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEEM CABINETS, INC. in 3835 S PITTSBURG AVE., HOMOSASSA, FL 34448 (NAICS 337110). OSHA activity number 339848400.

Watch Deem Cabinets, INC. — free Get an email when a new federal OSHA severe-injury report for Deem Cabinets, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
DEEM CABINETS, INC.
Site address
3835 S PITTSBURG AVE.
City
HOMOSASSA
State
FL
ZIP
34448
Mailing
3835 S PITTSBURG AVE., HOMOSASSA, FL 34448
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
12
Ownership type
A

11 citations on file for this inspection.

1910.213 C01

Serious Gravity 10 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $2940.00 Reduced
29 CFR 1910.213(c)(1): Circular handfed ripsaw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut:     a. At the shop, employees were exposed to struck by hazards, in that, two Delta table saws were used without being provided with a guard that would enclose the blade protruding from the table.
Recent events (2)
  • — I (S) $2940
  • — Z (S) $4900

1910.213 H01

Serious Gravity 10 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $4900.00 · Current $2940.00 Reduced
29 CFR 1910.213(h)(1): The sides of the lower exposed portion of the blade of radial saw(s) were not guarded to the full diameter of the blade by a device that automatically adjusted itself to the thickness of the stock and remained in contact with the stock being cut to give the maximum protection possible:    a. Shop area, employees were exposed to struck-by hazards, in that, a Delta radial arm saw model D047 and serial number 1424021310014 was not provided with a lower blade guard.
Recent events (2)
  • — I (S) $2940
  • — Z (S) $4900

1910.213 H04

Serious Gravity 10 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.213(h)(4): Radial saw(s) were not installed in a manner so as to cause the cutting head to return gently to the starting position when released by the operator:     a. Shop area, employees were exposed to struck-by hazards, in that, a Delta radial arm saw was not installed in a manner that would cause the cutting head to return to the starting position.    b. Shop area, employees were exposed to struck-by hazards, in that, a Craftsman radial arm saw was not installed in a manner that would cause the cutting head to return to the starting position.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.242 B

Serious Gravity 1 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a. At the shop, employees were exposed to a struck-by hazard, in that, compressed air used for cleaning was at 100 p.s.i..
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.303 F02

Serious Gravity 1 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a. At the breaker panels on the east wall in the shop, employees were exposed to electrical hazards, in that, three breaker panels had a total of 19 breakers without a label indicating their propose.    b. At the secondary breaker panels, employees were exposed to electrical hazards, in that, two breaker panels had a total of 22 breakers without a label indicating their propose.    c. At the breaker panel on the north wall, employees were exposed to electrical hazards, in that, 4 breakers were without a label indicating their propose.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.304 F01 VIII

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD."    a. At the breaker panels on the east wall in the shop, employees were exposed to electrical hazards, in that, breakers used to control the fluorescent lighting on a daily basis were not designed for the purpose they were used.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 B01 II

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:     a. At the breaker panels on the east wall in the shop, employees were exposed to electrical hazards, in that, two breaker openings were not covered.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 C04

Serious Gravity 1 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.305(c)(4): Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface:    a. At the shop storage room, employees were exposed to an electrical hazard, in that, a light switch for the room was not provided with a faceplate.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 G01 IV A

Serious Gravity 1 3 instances 12 exposed
Issued
Abate by
Penalty
Initial $2100.00 · Current $1260.00 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    a. At the shop, employees were exposed to an electrical hazard, in that, a red extension cord was used to provide power to a radial arm saw.    b. At the north side of the shop, employees were exposed to an electrical hazard, in that, a red extension cord was used to provide power to a dust collector.    c. At the north wall of the shop near the roll up door, employees were exposed to an electrical hazard, in that, a red extension cord was used to provide power to spot light.
Recent events (2)
  • — I (S) $1260
  • — Z (S) $2100

1910.305 G01 IV D

Serious Gravity 1 2 instances 12 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:    a. At the north side of the shop, employees were exposed to an electrical hazard, in that, a red extension cord was used to provide power to a dust collector by attaching it to the building wall.  b. At the north wall of the shop near the roll up door, employees were exposed to an electrical hazard, in that, a red extension cord was used to provide power to spot light by attaching it to the building.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01

Repeat Gravity 5 1 instance 12 exposed
Issued
Abate by
Penalty
Initial $5600.00 · Current $3360.00 Reduced
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:     a. At the shop area, employees were exposed to an electrical hazard, in that, a Linca boring machine was stored directly in front of three power panels therefore blocking access to the panels and disconnects which controlled the machines in the area.     The Deem Cabinets, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1) which was contained in OSHA inspection number 316177194 , citation number 2, item number 6, with respect to a workplace located at 6843 N Citrus Ave, Crystal River, Fl. 34428, and became a final order of the Review Commission on 01/03/ 2012.
Recent events (2)
  • — I (R) $3360
  • — Z (R) $5600

View DEEM CABINETS, INC.'s full OSHA safety record →