PAGO PAGO, AS —
OSHA Inspection: PARAMOUNT BUILDER'S INC.
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of PARAMOUNT BUILDER'S INC. in LBJ TROPICAL MEDICAL CENTER PSYCHIATRIC CENTER FAGAALU, EASTERN AMERICAN SAMOA, PAGO PAGO, AS 96799 (NAICS 237110). OSHA activity number 339852741.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PARAMOUNT BUILDER'S INC.
- Site address
- LBJ TROPICAL MEDICAL CENTER PSYCHIATRIC CENTER FAGAALU, EASTERN AMERICAN SAMOA
- City
- PAGO PAGO
- State
- AS
- ZIP
- 96799
- Mailing
- P.O. BOX 2070, PAGO PAGO, AS 96799
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 237110
- Employees
- 130
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.350 A09
- Issued
- Nov 7, 2014
- Penalty
- Initial $2,970 · Current $2,079 Reduced
General-duty citation text
29 CFR 1926.350(a)(9): Compressed gas cylinder(s) were not secured in an upright position a. On July 17, 2014 in the maintenance shop, oxygen and acetylene cylinders were not secured while being stored in an upright position to prevent them from being knocked over.
Recent events (2)
- — I (S) $2079
- — Z (S) $2970
1926.350 A10
- Issued
- Nov 7, 2014
- Abate by
- Nov 20, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.350(a)(10): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour: a. On July 17, 2014 at the maintenance shop, oxygen and acetylene cylinders were stored together exposing employees to a fire hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.403 I02 I
- Issued
- Nov 7, 2014
- Penalty
- Initial $2,970 · Current $2,079 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures: a. On July 17, 2014, next to the maintenance shop, a circuit breaker panel was missing a cover exposing employees to live electrical and arc flash hazards.
Recent events (2)
- — I (S) $2079
- — Z (S) $2970
More inspections at Paramount Builder'S INC.
View Paramount Builder'S INC.'s full OSHA safety record →
More inspections in this industry (NAICS 237110)
More inspections in AS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339852741.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.