Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,198,892Inspections Most recent open 2026-09-03 Last loaded 2026-09-07

OSHA Inspection: BUNGE NORTH AMERICA

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUNGE NORTH AMERICA in 751 E. FARMING STREET, MARION, OH 43302 (NAICS 424510). OSHA activity number 339862955.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bunge North America for free Get an email when a new federal OSHA severe-injury report for Bunge North America is published. One employer, no account, unsubscribe in one click.
Establishment
BUNGE NORTH AMERICA
Site address
751 E. FARMING STREET
City
MARION
State
OH
ZIP
43302
Mailing
751 E. FARMING STREET, MARION, OH 43302
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
11
Ownership type
Private (A)

1 citation on file for this inspection.

1910.137 B02 VIII

Serious Gravity 10 1 instance 1 exposed
Issued
Oct 1, 2014
Abate by
Oct 10, 2014
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.137(b)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests in accordance with Tables I-5 and I-6:         (a)  Bunge North America, 751 E. Farming Street, Marion, Ohio:  On or about May 7, 2014, the employer did not ensure that the electrical protective gloves used by an employee when replacing the motor on the outbound sampler were tested every 6 months.  The Salisbury gloves were most recently tested on February 21, 2013 and had been used by the employee since that date.  The employee was at risk of serious injury from electrical shock hazards while verifying that the motor's 480 volts AC; 3-phase circuit was energized.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

View Bunge North America's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339862955.