OSHA Inspection: E.J. FIELDS MACHINE WORKS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of E.J. FIELDS MACHINE WORKS, INC. in 816 FRONT STREET, MORGAN CITY, LA 70380 (NAICS 332710). OSHA activity number 339863342.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch E.J. Fields Machine Works, INC. — free Get an email when a new federal OSHA severe-injury report for E.J. Fields Machine Works, INC. is published. One employer, no account, unsubscribe in one click.
Site address
816 FRONT STREET
City
MORGAN CITY
State
LA
ZIP
70380
Mailing
P.O. BOX 608, MORGAN CITY, LA 70381
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332710
Employees
29
Ownership type
A

4 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 4 instances 5 exposed
Issued
Aug 21, 2014
Penalty
Initial $4,200 · Current $2,520 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  On or about July 21, 2014 the employer did not ensure that circuit breakers in Building 1 used as light switches were listed and labeled for use as such exposing employees to potential electrical shock and/or electrocution hazards.
Recent events (2)
  • — I (S) $2520
  • — Z (S) $4200

1910.305 D02

Serious Gravity 5 1 instance 5 exposed
Issued
Aug 21, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front.  On or about July 21, 2014 the employer did not ensure that an unused space in an electrical panel was appropriately dead front thus exposing employees to electrical shock and/or electrocution hazards
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 G01 V

Other-than-serious 1 instance 1 exposed
Issued
Aug 21, 2014
Abate by
Sep 5, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not clearly marked for identification of functions:  On or about July 21, 2014 the employer did not ensure that a pendant operating an overhead crane unit in Building 4 was clearly marked for identification of functions.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 F01

Other-than-serious 1 instance 5 exposed
Issued
Aug 21, 2014
Penalty
Initial $700 · Current $420 Reduced
29 CFR 1910.303(f)(1): Each disconnecting means required by Subpart S of Part 1910 for motors and appliances was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  On or about July 21, 2014 the employer did not ensure that an electrical panel in the Fabrication Shop (Building 1)  was adequately labeled to indicate the purpose of each circuit breaker, exposing employees to potential electrical shock and/or electrocution.
Recent events (2)
  • — I (O) $420
  • — Z (O) $700

View E.J. Fields Machine Works, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339863342.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.