OSHA Inspection: CASSENS TRANSPORT COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CASSENS TRANSPORT COMPANY in 24777 HONDA PARKWAY, MARYSVILLE, OH 43040 (NAICS 484230). OSHA activity number 339875619.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Cassens Transport Company — free Get an email when a new federal OSHA severe-injury report for Cassens Transport Company is published. One employer, no account, unsubscribe in one click.
Site address
24777 HONDA PARKWAY
City
MARYSVILLE
State
OH
ZIP
43040
Mailing
24777 HONDA PARKWAY, MARYSVILLE, OH 43040
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484230
Employees
1533
Ownership type
A

7 citations on file for this inspection.

1910.110 F02 II

Serious Gravity 5 1 instance 45 exposed
Issued
Sep 9, 2014
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.110(f)(2)(ii): Containers when stored inside shall not be located near exits, stairways, or in areas normally used or intended for the safe exit of people.    a. In bay 1 the emergency exit had two acetylene cylinders within 2 feet of the emergency exit. Employees were exposed to a fire/explosion hazard.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3400

1910.305 G01 IV B

Serious Gravity 5 1 instance 50 exposed
Issued
Sep 9, 2014
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.305(g)(1)(iv): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used:  29 CFR 1910.305(g)(1)(iv)(B): Where run through holes in walls, ceilings, or floors;    a. In the Drivers break room the flexible cord for the TV was run through the ceiling tile. Employees were exposed to a fire hazard.
Recent events (2)
  • — I (S) $1700
  • — Z (S) $3400

1910.305 G02 III

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 9, 2014
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.    a. The flexible cord for the Miller CS-300 Arc Welder was not provided strain relief at the plug. Employees were exposed to 240Volt 32 Amp electrical current.
Recent events (2)
  • — I (S) $2125
  • — Z (S) $4250

1910.334 A02 II

Serious Gravity 5 1 instance 30 exposed
Issued
Sep 9, 2014
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made.    a. At the fuel island the flexible cord for the pump that handles the Diesel exhaust fluid was damaged and the employer wrapped it in electrical tape. The employees were exposed to contact with electrical current.
Recent events (2)
  • — I (S) $2125
  • — Z (S) $4250

1910.157 E02

Other-than-serious 1 instance 67 exposed
Issued
Sep 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable extinguishers or hose used in lieu thereof under paragraph (d)(3) of this section shall be visually inspected monthly.  a. Through out the facility the employer failed to perform monthly visual inspection of the fire extinguishers. Employees were exposed to a fire hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B01 II

Other-than-serious 1 instance 15 exposed
Issued
Sep 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed.  a. The bay 4 motor control box had an unused opening at the bottom, thereby exposing employees to a contact with electrical current hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.307 C02

Other-than-serious 2 instances 10 exposed
Issued
Sep 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. Requirements for each of these options are as follows:  29 CFR 1910.307(c)(2): Approved for the hazardous (classified) location.  a. In the garage pit 5 the employer had a non rated switch wired to a flexible cord that powered a sump pump. The switch was not rated for Class 1 hazardous location. The employees were exposed to a fire/explosion hazard.  b. In the garage pit 6 the employer had a non rated switch wired to a flexible cord that powered a sump pump. The switch was not rated for Class 1 hazardous location. The employees were exposed to a fire/explosion hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Cassens Transport Company's full OSHA safety record →