OSHA Inspection: AQUILA SEDCO DRILLING COMPANY, LP

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AQUILA SEDCO DRILLING COMPANY, LP in REEVES 2723 LEASE, WELL #2SWD, RIG 3, 3 MILES N OF PECOS, TX, PECOS, TX 79772 (NAICS 213111). OSHA activity number 339877557.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Aquila Sedco Drilling Company, LP for free Get an email when a new federal OSHA severe-injury report for Aquila Sedco Drilling Company, LP is published. One employer, no account, unsubscribe in one click.
Site address
REEVES 2723 LEASE, WELL #2SWD, RIG 3, 3 MILES N OF PECOS, TX
City
PECOS
State
TX
ZIP
79772
Mailing
2525 KELL BLVD., SUITE 405, WICHITA FALLS, TX 76308
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213111
Employees
92
Ownership type
A

5 citations on file for this inspection.

1910.303 G01 VII B

Serious Gravity 5 4 instances 6 exposed
Issued
Oct 29, 2014
Abate by
Nov 4, 2014
Penalty
Initial $3,500 · Current $3,500
29 CFR 1910.303(g)(1)(vii)(B): The employer did not ensure that outdoor electrical equipment was protected from accidental contact by vehicular traffic.  Drill Site: On or about July 29, 2014, and at times prior thereto, the employer did not protect the 480 volt 8/4 AWG flexible cords extending from the transformer to the drilling rig from damage caused by vehicles. This condition exposed the employees to electrical hazards.
Recent events (1)
  • · Z (S) $3500

1910.305 A02 X

Serious Gravity 5 2 instances 5 exposed
Issued
Oct 29, 2014
Abate by
Nov 4, 2014
Penalty
Initial $3,500 · Current $3,500
29 CFR 1910.305(a)(2)(x):  Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points:  On or about July 29, 2014, and at times prior thereto, The 240 volt 8/4 AWG flexible cord running from one side of the change house to the other was not protected when going through unprotected wall openings. This condition exposed the employees to an electrical hazard.
Recent events (1)
  • · Z (S) $3500

1910.305 G01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 29, 2014
Abate by
Nov 4, 2014
Penalty
Initial $3,500 · Current $3,500
29 CFR 1910.305(g)(1)(i): Flexible cords and cables were not approved for conditions of use and location:  Drill site: On or about July 29, 2014, and at times prior thereto, the employer had the crew use a wall mounted electrical connection to connect two 480 volt 8/4 AWG flexible cords together, to feed power to the drilling rig approximately 200-feet from the transformer. This condition exposed the employees to an electrical hazard.
Recent events (1)
  • · Z (S) $3500

1910.305 G02 III

Serious Gravity 5 2 instances 5 exposed
Issued
Oct 29, 2014
Abate by
Nov 4, 2014
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:     Drill Site: On or about July 29, 2014, the strain relief to the outlet hanging outside the change house by the door was damaged. This condition exposed the employees to electrical hazards.
Recent events (1)
  • · Z (S) $2800

1910.334 A02 I

Repeat Gravity 5 4 instances 5 exposed
Issued
Oct 29, 2014
Abate by
Nov 4, 2014
Penalty
Initial $5,600 · Current $5,600
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  Drill site: On or about July 29, 2014, and at times prior thereto, the employer failed to inspect the 480 volt 8/4 AWG flexible cord for damage prior to use. The flexible cord stretched from the transformer across 200-feet to the drilling rig while maintenance was performed. This condition exposed the employees to electrical hazards.  The Aquila Drilling Co., LP was previously cited for a violation of this occupational safety and health standard 1910.334(a)(2)(I), which was contained in OSHA inspection number 313502536, citation number 1, item number 4 and was affirmed as a final order on March 14, 2012, with respect to a workplace located at Annie Oakley 23-1, Rig 3 Pecos, TX 79772.
Recent events (1)