Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: AQUA PENNSYLVANIA, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AQUA PENNSYLVANIA, INC. in 2520 W. LINCOLN HWY., OAKFORD, PA 19053 (NAICS 221310). OSHA activity number 339880098.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Aqua Pennsylvania, INC. — free Get an email when a new federal OSHA severe-injury report for Aqua Pennsylvania, INC. is published. One employer, no account, unsubscribe in one click.
Site address
2520 W. LINCOLN HWY.
City
OAKFORD
State
PA
ZIP
19053
Mailing
762 W. LANCASTER AVE., BRYN MAWR, PA 19010
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221310
Employees
16
Ownership type
A

1 citation on file for this inspection.

1910.119 J04 II

Other-than-serious 1 instance 2 exposed
Issued
Nov 21, 2014
Abate by
Dec 19, 2014
Penalty
Initial $4,000 · Current $4,000
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices :    a) Neshaminy Water Treatment Plant, chlorine evaporator, pressure relief valve  On or about July 23, 2014, The inspection and testing frequency of the pressure relief valve on the chlorine evaporator was not consistent with good engineering practices such as the National Board Inspection Code.  The document referenced in the employer's Mechanical integrity program (Section 4.14 of WT.050.200.001.UA.IM.0411) did not include inspection and testing procedures or frequency, nor did the employer have testing and inspection procedures or history for this pressure relief valve.       Abatement Note: The National Board Inspection Code recommends an initial five year interval for inspection and testing for a pressure relief valve in combination with a rupture disk such as in this installation; this interval may be modified based on previous inspection history. Section 2.5, pages 47 thru 55 of the 2007 NBIC provides detailed and specific requirements for inspection and testing.
Recent events (2)
  • — I (O) $4000
  • — Z (S) $4000

View Aqua Pennsylvania, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339880098.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.